11
Cutoff current setting mode
C U T A
Mode defines load current that does not measured (Cutoff current).
Use to avoid miss-measurement by wiring or induction noise at no-load.
0.00kW is displayed for instantaneous electric power, 0.0A is displayed for current. Integrated
electrical energy is not measured.
・
It can be set the range of 1.0% to 50.0%.
ex) When set to 10.0, current under 10.0%F.S is not measured.
Unit for pulse output setting mode (Power)
P L - P
Mode defines unit used for pulse output.
・
Select from 0.001/0.01/0.1/1/10/100kWh /Alarm.
When “ALARM” is set, alarm is output at the time when instantaneous electric power is over the
setting value.
When one of the “0.001/0.01/0.1/1/10/100”[kWh] is set, one pulse is output at the setting value.
Alarm value setting mode
A L - P
Mode defines instantaneous electric power used for alarm output.
・
It is set the range of 0.00 to 9999.99kW.
※
This mode is only when “ALARM” is selected on unit for pulse output setting mode.
Electricity charge setting mode
P Y
/
$
/
E U R
/
C N Y
/
C H G
/
C O 2
Mode defines electricity charge ratio and conversion factor used as a standard per 1kWh.
The electricity charge ration of 5 kinds of currency (JPY,
$
,EUR,CNY,CHG) and CO
2
conversion
factor can be set.
・
It can be set the range of 0.0 to 99.9 yen/1kWh. (Initial 10.0)
・
It can be set the range of 0.000 to 9.999 dollars/1kWh. (Initial 0.093)
・
It can be set the range of 0.000 to 9.999 euros/1kWh. (Initial 0.085)
・
It can be set the range of 0.00 to 99.99 yuan/1kWh. (Initial 10.00
)
・
It can be set the range of 0.00 to 99.99 /1kWh. (Initial 10.00
)
・
CO
2
conversion factor can be set the range of 0.000 to 9.999 kg-CO
2
/1kWh. (Initial 0.410
)
Normal
display
↓
<MODE>
MODE
display
↓
<kW/kWh>
CT type setting mode
Factory setting / Display
・
Press
<kW/kWh>
to change CT type.
・
CT type is selected from 50
→
100
→
250
→
400
→
5
↓
<SET>
Primary side current of CT setting mode
Factory setting / Display
・
Enter primary side current of CT using
<kW/kWh>,< A >, < V >
.
・
If measured CT is 100A/5A, set to 100.
・
If 5A is measured, set to 5.
It is only when
“5A” is selected on CT type setting mode.
↓
<SET>