KW1M-H Eco-POWER METER
74
8.5 Main Unit Memory Specifications
Logging Function
File type 1
(Instantaneous
value)
*1
Save cycle
60 minutes (Just at every hour) (fixed)
Saved data
(Instantaneous value)
Integrated electric power, Instantaneous electric power,
Current, Voltage, Power factor, Frequency, Count value
Saved data
amount
24 records for 1 file (Max 1.5 years)
File type 2
(Difference value)
*1
Save cycle
60 minutes (Just at every hour) (fixed)
Saved data
(Difference value) Integrated electric power, Count value
Saved data
amount
24 records for 1 file (Max 1.5 years)
File type 3
(Detail instantaneous
value)
*1 Save cycle
Selectable from 1min, 5min, 10min, 15min, 30min, 60min.
(Saved timing)
1min selected: Just at every minute
5min selected: 00,05,10,15,20,25,30min
・・・
of every hour
10min selected: 00,10,20,30,40,50min of every hour
15min selected: 00,15,30,45min of every hour
60min selected: Just at every hour
Saved data
(Instantaneous value)
Integrated electric power, Instantaneous electric power,
Current, Voltage, Power factor, Frequency, Count value
Electric power converted by pulse, Present demand,
Load ON-time, Load OFF-time
Saved data
amount
Max. 5760 records about 4 days
(In case of 1 min of save cycle)
Display
Monthly integrated electric power (Latest 18 months)
Daily integrated electric power (Latest 30 days)
Hourly integrated electric power (Latest 24 hours)
Calendar timer
Time accuracy *2
・
with clock correction
Synchronize with frequency of measured voltage *3
・
without clock correction
(Monthly accuracy)
±
240 seconds (at -10
℃
)
±
70 seconds (at 25
℃
)
±
240 seconds (at 50
℃
)
Backup contents by battery
Time measurement and log data storage
Battery life *4
About 2 years (at 25
℃
) (when no power)
*1 You can select if the data of file type 1,2 and 3 is written to SD memory card with the setting mode.
*2 With using clock correction function, it synchronizes with the measured voltage (50Hz/60Hz) automatic
recognition and corrects the clock. In case of a power failure, it measures time by using the internal clock
and backup battery. In this case the accuracy is applied to the accuracy without clock correction.
You can select if it corrects a clock or not with the setting mode.
*3 The reference frequency for using the time synchronizes is the frequency of measured voltage input to
P1-P0 terminals. It doesn’t correct the time when P1-P0 terminals are not connected. In case of that it
detects an abnormal for the reference frequency; it will shift to the internal clock. When it detects a normal
frequency after that, it synchronizes with the frequency of measured voltage and corrects the time.
*4 When battery power is reduced, ‘BATT’ is blinking. Replace battery according to the procedures.
Battery life will be short if using this under high-temperature.