KW1M-H Eco-POWER METER
62
Data register
Name
Unit
Kind of data
Range
R/W
DT00100
Integrated electric
power
0.01kWh
Unsigned 32bit
0 to 999999999
R/W
DT00101
DT00107
R-current
0.1A
Unsigned 16bit
0 to 60000
R
DT00108
S-current
0.1A
Unsigned 16bit
0 to 60000
R
DT00109
T-current
0.1A
Unsigned 16bit
0 to 60000
R
DT00111
Power factor
0.01
Signed 16bit
-99 to 100
R
DT00112
Frequency
0.1Hz
Unsigned 16bit
0 to 1000
R
DT00118
Integrated electric
power converted by
pulse
0.01kWh
Unsigned 32bit
0 to 999999999
R/W
DT00119
DT00146
Pulse constant number
-
Unsigned 16bit
0; 50000pulse/kWh
1; 2000pulse/kWh
R/W
DT00147
Reference frequency
0.1Hz
Unsigned 16bit
475 to 630
R/W
DT00150
Load ON-time
0.1h
Unsigned 32bit
0 to 999999
R/W
DT00151
DT00152
Load OFF-time
0.1h
Unsigned 32bit
0 to 999999
R/W
DT00153
DT00154
Pulse count value
-
Unsigned 32bit
0 to 999999
R/W
DT00155
DT00156
Pulse rate
0.01kWh
Unsigned 32bit
1 to 100000
R/W
DT00157
DT00158
Preset value
-
Unsigned 32bit
0 to 999999
R/W
DT00159
DT00160
Prescale value
0.001
Unsigned 32bit
0 to 100000
R/W
DT00161
DT00162
Max. counting speed
Hz
Unsigned 16bit
30, 2000
R/W
DT00163
Auto-off time
min
Unsigned 16bit
0 to 99 (0:always on)
R/W
DT00170
R(RS)-voltage
0.1V
Unsigned 32bit
0 to 999999
R
DT00171
DT00172
S(RT)-voltage
0.1V
Unsigned 32bit
0 to 999999
R
DT00173
DT00174
T(TS)-voltage
0.1V
Unsigned 32bit
0 to 999999
R
DT00175
DT00176
Instantaneous
electric power
0.01kW
Unsigned 32bit
0 to 999999
R
DT00177
DT00200
Present demand
0.01kW
Unsigned 32bit
0 to 99999999
R
DT00201
DT00202
Demand remaining time
Minute
Unsigned 16bit
0 to 30
R
DT00203
Estimated demand
0.01kW
Unsigned 32bit
0 to 99999999
R
DT00204
DT00205
Demand setting value
0.01kW
Unsigned 32bit
0 to 999999
R/W
DT00206
*1 When ‘P-THR’ is selected on Unit for pulse output setting mode, this is used for demand alarm
status.
Note1) R: Read W: Write
2) Data register except specified is 0.
3) If each setting value is wrote by communication, it memories to internal EEPROM at the same
time. Therefore, change setting frequently makes EEPROM’s life short. Avoid to usage like this.
4) Write a data within the range when you write it.
5) Max reading point is 26 points (57 bytes), max writing point is 23 points (55 bytes).
6) Unit of data in DT00118 and DT00119 is 0.01kWh. It is different from the display.