KW1M-H Eco-POWER METER
49
kWh kWh MWh MWh
0.000 999999 1000.00 9999.99
6.2.10 Pulse input value
・
It displays present pulse input value.
・
Press <SHIFT/
▽
> to change pulse counter and electric power converted by pulse.
*Electric power converted by pulse is displayed when ‘PM’ is selected with power input type setting
mode.
*Only when you change Power input type ‘CT’ to ‘PM’, or ‘PM’ to ‘CT’ during the same period,
it displays both of pulse count value and electric power converted value measured until then.
Sample
Pulse counter
Electric power
converted by pulse (kWh)
Prescale: 0.01
Electric power
converted by pulse (MWh)
・
Pulse counter is counted and displayed 0 to 999999 for pulse counter.
*After reaching the full scale (999999), the value reverts to 0 but continues to measure.
・
Electric power converted by pulse is measured and displayed from 0.000kWh to 9999.99MWh.
・
The decimal point and unit are changed automatically.
(After reaching the full scale (9999.99MWh), the value reverts to 0.00kWh but continues to measure.)
How to Reset
・
Hold down <SET> and press <MODE> makes pulse input value clear.
Reset
<SET>
ON
OFF
<MODE>
ON
OFF