KW1M-H Eco-POWER METER
23
Mode2 Setting flow chart
Monitor
↓
<MODE> (MODE 2 Lighting)
↓
<SET>
Max. counting speed setting mode
*Skip when ‘P-THR’ is selected on Unit for pulse output setting mode
Press <ITEM/
△
><SHIFT/
▽
> to change 2000(2kHz)
⇔
30(30Hz).
2000(2kHz)
30(30Hz)
↓
<SET>
Pre-scale setting mode
Set pre-scale value using <ITEM/
△
><SHIFT/
▽
>.
(0.001 to 100.000, initial 1.000)
*The decimal point set with this mode is applied to count value and preset value.
↓
<SET>
Power input type setting mode
Press <ITEM/
△
><SHIFT/
▽
> to change CT
⇔
PM.
CT (CT input)
PM (Pulse input)
↓
<SET>
Pulse type setting mode
*It is only when ‘PM’ is selected on power input type setting mode.
Press <ITEM/
△
><SHIFT/
▽
> to change kWh
⇔
PULSE.
kWh
PULSE
↓
<SET>
Pulse rate setting mode
*It is only when ‘kWh’ is selected on pulse type setting mode.
Set the rate per 1pulse using <ITEM/
△
><SHIFT/
▽
>.
(0.001 to 100.000 Initial: 1.000)
↓
<SET>
Pulse constant value setting mode
*It is only when ‘PULSE’ is selected on pulse type setting mode.
Press <ITEM/
△
><SHIFT/
▽
> to change 50000
⇔
2000.
50000
2000
↓