PLEASE READ PRIOR TO INSTALLING THIS FAN

These fans are also built to take care of the homeowner’s spot ventilation needs when the room is 
occupied. The basic fan models allow a choice of three speeds. When fans are equipped with the optional 
Multi-Speed module, these models kick up to a maximum level of 150 CFM for the FV-11-15VK1 and 110 
CFM for the FV-05-11VKS1 and FV-05-11VK1 either when the switch is turned on or activated by the 
optional Condensation Sensor module or the optional Motion Sensor module.

A High/Low Delay Timer, located inside the fan unit, is utilized to return the fan back to the pre-set
Continuous ventilation mode. The installer needs to consult with the homeowner for the desired
setting on the timer (0 - 60 minutes) and make the adjustments during the installation.

CustomVent Multi-Speed module (Lower Setting).   ASHRAE 62.2-2010

(sq.feet)

<1,000

1,500
2,000
2,500
3,000
3,500
4,000
4,500
5,000
5,500
6,000
6,500
7,000

33
38
43
48
53
58
63
68
73
78
83
88
93

40
45
50
55
60
65
70
75
80
85
90
95

100

48
53
58
63
68
73
78
83
88
93
98

103
108

55
60
65
70
75
80
85
90
95

100
105
110

Two Bedrooms Three Bedrooms Four Bedrooms

Five Bedrooms

DESCRIPTION

These products are listed by UL under UL file No. E78414.
These products use a sirocco fan driven by a DC motor powered by an integral transformer. The motor is
designed to have long operating life, high dynamic response, higher speed ranges with saving energy.
The grille covering the fan body is a spring-loaded, quick remove type. A damper for preventing air counter
flow is provided. The blower uses a high-capacity sirocco fan developed to reduce the noise level.

UNPACKING

Unpack and carefully remove the unit from carton.
Refer to the Supplied Accessories list to verify that all parts are present.

Spot and Continuous Ventilation:

   These fans are designed to run continuously ensuring a healthy

environment at low CFM levels 24 hours a day. By utilizing the optional CustomVent Multi-Speed 

module the fans are built to run continuously at a pre-set lower level (FV-05-11VKS1 and FV-05-11VK1: 

0, 30, 40, 50, 60, 70, 80, 90, 100 CFM; FV-11-15VK1: 0, 50, 60, 70, 80, 90, 100, 110, 120 CFM). The 

setting is dependent on the size of the house and the individual wishes of the homeowner. It is crucial 

that the installer pre-set the lower setting during the installation. Please refer to the chart below 

and the switch indication on page 6. 

Содержание FV-05-11VKS1

Страница 1: ...IPTION UNPACKING SUPPLIED ACCESSORIES DIMENSIONS WIRING DIAGRAM FEATURE INDICATION PLUG N PLAY FUNCTION DEVICES MOTION PLUG N PLAY FUNCTION DEVICES INSTALLATION PLUG N PLAY FUNCTION DEVICES INSTALLATI...

Страница 2: ...d shower enclosures For Your Safety To reduce the risk of injury loss of life electric shock fire malfunction and damage to equipment or property always observe the following safety precautions Explan...

Страница 3: ...r dedicated parts such as mounting fixtures must be used if such parts are provided Do not install the unit where ducts are configured as shown in Fig A Adaptor CAUTION Canada only Not to be installed...

Страница 4: ...100 105 110 Two Bedrooms Three Bedrooms Four Bedrooms Five Bedrooms DESCRIPTION These products are listed by UL under UL file No E78414 These products use a sirocco fan driven by a DC motor powered b...

Страница 5: ...V 11 15VK1 4 5 8 116 7 8 22 5 1 26 FV 11 15VK1 10 11 12 11 FV 05 11VKS1 Unit inches mm 13 330 3 1 4 81 3 1 2 88 7 3 8 190 6 3 8 163 5 7 8 148 5 7 8 148 3 7 8 98 10 1 4 260 12 1 8 307 10 1 4 260 3 7 8...

Страница 6: ...the high speed setting Selecting a particular TIME option will cause the fan to run for the selected amount of time before returning to the lower speed setting chosen on the CFM dial Pick A Flow CFM M...

Страница 7: ...ecessary to connect wall switch when only plug in FV NLVK1 fan can operate on high speed with wall switch control fan can also operate on low speed when used in combination with the FV VS15VK1 INDICAT...

Страница 8: ...plug connector from receptacle and remove adaptor from fan body by removing the machine screw M4X6 before installation Fig 1 IMPORTANT Remove the tape from damper and adaptor before installation As sh...

Страница 9: ...page 5 Follow all the local electrical safety codes as well as the National Electrical Code NEC Using UL approved wire nuts connect house power wires to ventilating fan wires Fig 5 Fig 5 FV 05 11VKS1...

Страница 10: ...1 Remove the existing fan and cut ceiling openning 2 Follow the step 1 4 5 on page 8 and step 7 on page 9 Before connect the circular duct to the adaptor should pull down the circular duct from the c...

Страница 11: ...FV MSVK1 or FV NLVK1 Pull down the mounting spring that without lead wire passed side and remove motion sensor or LED night light as shown in Fig 16 Squeeze mounting spring and pull down carefully Dis...

Страница 12: ...d directly over the fan housing in the attic Our fans and fan light combination units do not create excessive heat that is a common problem with recessed light fixtures or some competitor s fan light...

Отзывы: