![Panasonic FP7 Series Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/panasonic/fp7-series/fp7-series_additional-functions-manual_3529967042.webp)
Multi Connection Server Function
6-4
6.1.2 Precautions When Connecting Multi Connection Servers
When connecting to a connection on which a multi connection server has been set, if the
maximum number of clients connectable have been already connected, it cannot be
connected to the target server port.
When connecting an additional client to the multi connection server to which the maximum
number of clients have been already connected, the disconnecting operation is repeated right
after the connection on the client side.
When the FP7 is the client, the master communication clear to send flag (X90 for connection
1) repeatedly turns ON and OFF.