High-level Instructions
3-4
Processing
Example 1) When the operation unit is signed 16-bit (SS)
S1: DT0, S2: DT3, D: DT10
DT0
-2(FFFEh)
DT10
・
DT11
-2(
FFFF
FFFEh)
DT1
-1(FFFFh)
DT12
・
DT13
-1(
FFFF
FFFFh)
DT2
0(0000h)
DT14
・
DT15
0(
0000
0000h)
DT3
1(0001h)
DT16
・
DT17
1(
0000
0001h)
DT4
DT18
・
DT19
Example 2) When the operation unit is unsigned 16-bit (US)
S1: DT0, S2: DT3, D: TS0
DT0
65534(FFFEh)
TS0
65534(
0000
FFFEh)
DT1
65535(FFFFh)
TS1
65535(
0000
FFFFh)
DT2
0(0000h)
TS2
0(
0000
0000h)
DT3
1(0001h)
TS3
1(
0000
0001h)
DT4
TS4
Precautions during programming
In the case of a direct address and index modification address, specify the same type of
device for [S1] and [S2]. Besides, specify [S2] to be equal to or larger than [S1].
The specified source area and destination area should not overlap each other.
Flag operation
Name
Description
Latest error
(SR7)
Hold error
(SR8)
To be set in case of out-of-range in indirect access (index modiication).
To be set when S1 is larger than S2.
To be set when the destination range is out of the accessible range.
To be set when the ranges of the source area and the destination area overlap.
Содержание FP7 Series
Страница 1: ...FP7 CPU Unit Ver 4 20 Additional Functions Manual 12 21 2015...
Страница 3: ...1 Introduction of Ver 4 20...
Страница 6: ......
Страница 7: ...2 Basic Instructions...
Страница 17: ...3 High level Instructions...
Страница 29: ...4 FP2 FP2SH Program Conversion Function...
Страница 36: ......
Страница 37: ...5 MEWTOCOL COM...
Страница 39: ...6 Multi Connection Server Function...