Basic
Instructions
2-8
When specifying a constant
- CT instruction
CT0
U100
X100
C0
Y131
X101
Count
Reset
CE0
U100
CS0
U100
U100 is set in the setting value area CS0 when compiling the program.
The setting value area CS0 is set in the elapsed value area CE0 when the input of X101 falls.
The setting range of a constant is U0 to U4294967295.
- CT16- instruction
CT16
-
0
U100
X100
C0
Y131
X101
Count
Reset
CE0
U100
CS0
U100
U100 is set in the setting value area CS0 when compiling the program.
The setting value area CS0 is set in the elapsed value area CE0 when the input of X101 falls.
The setting range of a constant is U0 to U65535.
Note)
When a 32-bit value is written into the elapsed value area CE while the counter is being
operated using an instruction such as MV instruction, the timer operates with the written 32-bit
value.
When a 32-bit value is written into the setting value area CS, the timer operates with the
written 32-bit value.
Precautions during programming
Both the counter setting value area CS and the counter elapsed value area CE occupy the
32-bit area.
When specifying a 16-bit device such as DT for the operation [S] of CT16- instruction, it is
used as 16-bit data.
When U0 is specified for the setting value, the count-up operation is performed when the
instruction is executed and the counter contact [C] turns ON.
Содержание FP7 Series
Страница 1: ...FP7 CPU Unit Ver 4 20 Additional Functions Manual 12 21 2015...
Страница 3: ...1 Introduction of Ver 4 20...
Страница 6: ......
Страница 7: ...2 Basic Instructions...
Страница 17: ...3 High level Instructions...
Страница 29: ...4 FP2 FP2SH Program Conversion Function...
Страница 36: ......
Страница 37: ...5 MEWTOCOL COM...
Страница 39: ...6 Multi Connection Server Function...