Input specifications
Item Specification
Input point
Up to 8 channels per unit (The number of Input points can be changed
2, 4, 6 and 8 channels are available.)
Thermocouple types K, J
-100.0
℃
to 500.0
℃
-148.0
℉
to 790.0
℉
*1
Thermocouple type T
-100.0
℃
to 400.0
℃
-148.0
℉
to 752.0
℉
*1
Input range
Thermocouple type R
0.0
℃
to 1500.0
℃
32.0
℉
to 1590.0
℉
*1
K and J (when using
℃
)
: K - 1000 to K 5000
K and J (when using
℉
)
: K - 1480 to K 7900
*1
When range over using(
℃
) : K -1001, K 5001 or K 8000
When range over using(
℉
) : K -1481, K 7901 or K 8000
(when the thermocouple Broken: K 8000)
*2
(Until the temperature can be measured at the initial startup: K 8001)
*3
T (when using
℃
)
: K - 1000 to K 4000
T (when using
℉
)
: K - 1480 to K 7520
*1
When range over using(
℃
) : K -1001, K 4001 or K 8000
When range over using(
℉
) : K -1481, K 7521 or K 8000
(when the thermocouple Broken: K 8000)
*2
(Until the temperature can be measured at the initial startup: K 8001)
*3
R (when using
℃
)
: K 0 to K 15000
R (when using
℉
)
: K 320 to K 15900
*1
When range over using(
℃
) : K 0, K 15001 or K 16000
When range over using(
℉
) : K 0, K 15901 or K 16000
Digital output
(when the thermocouple Broken: K 16000)
*2
(Until the temperature can be measured at the initial startup: K 16001)
*3
Resolution
0.1
℃
Sampling cycle
*5
300ms
: when using 2 channels for an input points
*4
500ms
: when using 4 channels for an input points
*4
700ms
: when using 6 channels for an input points
*4
900ms
: when using 8 channels for an input points
*4
Accuracy
Range for K and J (-100
℃
to 500
℃
)
:
±
0.8
℃
Range for T
(-100
℃
to 400
℃
) :
±
0.8
℃
Range for R
(0
℃
to 99.9
℃
) :
±
3
℃
(100
℃
to 299.9
℃
) :
±
2.5
℃
(300
℃
to 1500
℃
) :
±
2
℃
Input impedance
more than 1M
Ω
Insulation method
・
between thermocouple input terminals and Control Unit internal circuits
Photo-coupler insulation/DC-DC insulation
・
between thermocouple input terminal channels
PhotoMos relay insulation
Input/Output points
Input - 32 points 16 points for WX2, 4, 6: Analog input
CH0, 2, 4, 6 (WX2)
*6*7
16 points for WX3, 5, 7: Analog input
CH1, 3, 5, 7 (WX3)
*6*7
Output 32 points (reserved.)