5 Conversion Characteristic
-
K and J range (-100.0
℃
to 500.0
℃
)
-
T range (-100.0
℃
to 400.0
℃
)
When the input out of the range is made
When the input out of the range is made
Input
converted to
Input
converted to
-100.1
℃
Max.
K -1001
- 100.1
℃
Max.
K -1001
500.1
℃
Min.
K 5001 or K 8000
400.1
℃
Min.
K 4001 or K 8000
When the thermocouple
is broken
K 8000
When the thermocouple
is broken
K 8000
- R range (0.0
℃
to 1500.0
℃
)
When the input out of the range is made
Input converted
to
0.0
℃
Max.
K 0
1500.1
℃
Min.
K 15001 or K 16000
When the thermocouple
is broken
K 16000
6