9 Specifications
9.1
Specifications
-
General specifications
Item Specifications
Consumption current increased
for the Control Unit
25mA Max. (24V DC)
Operating ambient temperature
0
℃
to +55
℃
Storage ambient temperature
-20
℃
to +70
℃
Operating ambient humidity
30%RH to 85%RH (at25
°
C no condensing)
Storage ambient humidity
30%RH to 85%RH (at25
°
C no condensing)
Withstand voltage
between “all the thermocouple input terminals” and “all the Control
unit power/functional earth terminals”: 500V AC for 1min.
between thermocouple input terminal channels: 200V AC for 1 min.
Insulation resistance
between “all the thermocouple input terminals” and “all the Control
unit power/functional earth terminals”: more than 100M
Ω
(Testing voltage: 500V DC)
Vibration resistance
10Hz to 55Hz 1 sweep/min. with double amplitude in 0.75mm
for 10 min. on 3 axes (toward X, Y and Z directions)
Shock resistance
98m/s
2
for 4 times on 3 axes (toward X, Y and Z directions)
Noise immunity
1000V [P-P] Pulse width 50ns, 1µs (using noise simulator)
Operating condition
Must be free from corrosive gases and excessive dust.
Weight
about 85g (FP0-TC4)
about 95g (FP0-TC8)
14