![Panasonic FMU Скачать руководство пользователя страница 63](http://html.mh-extra.com/html/panasonic/fmu/fmu_technical-manual_262846063.webp)
Programming Information for Control FPWIN Pro
FMU Technical Manual
54
Connected to the output pin
SlavesDiagnostic_iHasError
is a variable of the type INTEGER.
The integer stores the error code.
Error
Indication
Network
Source
Recommendation
0
No error.
All
17
No response from slave.
PROFIBU
S
Slave
•
Check
network
wiring.
•
Check bus address of slave.
•
Check baud rate setting.
18
Master not in logical
token ring.
PROFIBU
S
Network in
general
•
Check master DP address or
highest-station address of other masters.
•
Examine bus wiring for short circuits.
161
Remote address
requested out of range.
All
Master
Check slave/node address in request
message.
5.3.7 SlaveDiagnostic_awData Output
The inputs and outputs found on the lower half of the function block help you diagnose
problems.
Connected to the output pin
SlaveDiagnostic_awData
is a variable of the type ARRAY [0...3]
of WORD.
In this example, the identifier is
DiagData
. This variable is used for all network types, but the
information stored in the variable is nevertheless network-specific:
Содержание FMU
Страница 1: ...programmable logic controller FMU Technical Manual ...
Страница 3: ......
Страница 9: ......
Страница 10: ...Chapter 1 Features and Restrictions ...
Страница 13: ......
Страница 14: ...Chapter 2 Parts and Functions ...
Страница 23: ......
Страница 24: ...Chapter 3 Specifications ...
Страница 30: ...Chapter 4 Installation and Wiring ...
Страница 42: ...Chapter 5 Programming Information for Control FPWIN Pro ...
Страница 70: ...Chapter 6 Outline Dimensions ...
Страница 73: ......
Страница 76: ...Record of Changes Manual No Date Description of changes ACGM0161V10EN July 2008 First edition ...