![Panasonic FMU Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/panasonic/fmu/fmu_technical-manual_262846050.webp)
FMU Technical Manual
5.3 FMU_DataExchange
41
5.3.1.2 GlobalBusStateField for DeviceNet
Identifier part
Identifier
Explanation
Global bits
GlobBit_Status
Lower byte of the WORD. Details follow the table.
Status
GlobBit_Status
Higher byte of the WORD.
The master system can be in one of the following states:
•
16#00:
OFFLINE
•
16#40:
STOP
•
16#80:
CLEAR
•
16#C0: OPERATE
Error remote address
ErrRemAddr_ErrEvent
Lower byte of the WORD.
If the global bits "control error, auto-clear error or
non-exchange error" are set, this variable indicates the
address of the device. If the error occurs in the FMU, the
value is 255. Otherwise the faulty device address = MAC
ID is stored.
Error event
ErrRemAddr_ErrEvent
Higher byte of the WORD.
Each error is assigned a number. The errors are
explained following the table.
Bus error count
BusErrorCnt
This variable is incremented whenever the error frame
counter of the Philips CAN chip used has reached the
warning limit due to disturbed bus communication.
Timeout count
TimeOutCount
This variable is incremented when the CAN chip reports
that it is no longer involved in bus activities because the
bus error frame counter has been exceeded. The chip
must be reinitialized, which is done automatically by the
FMU.
Server status
MoreInformation
Lower byte of ARRAY [0] of WORD.
The FMU is able to be a I/O server and master
simultaneously. The status of the server poll I/O
connection and the explicit connection can be read from
this variable.
•
Bit 0 = current status of the server explicit connection.
•
Bit 1 = current status of the server poll I/O connection.
•
Bits 2-7 are reserved.
Содержание FMU
Страница 1: ...programmable logic controller FMU Technical Manual ...
Страница 3: ......
Страница 9: ......
Страница 10: ...Chapter 1 Features and Restrictions ...
Страница 13: ......
Страница 14: ...Chapter 2 Parts and Functions ...
Страница 23: ......
Страница 24: ...Chapter 3 Specifications ...
Страница 30: ...Chapter 4 Installation and Wiring ...
Страница 42: ...Chapter 5 Programming Information for Control FPWIN Pro ...
Страница 70: ...Chapter 6 Outline Dimensions ...
Страница 73: ......
Страница 76: ...Record of Changes Manual No Date Description of changes ACGM0161V10EN July 2008 First edition ...