FMU Technical Manual
5.3 FMU_DataExchange
43
The following error numbers are valid for the error event if "Error remote address" is not equal to
255.
ErrEvent
Explanation
Source of error
Recommendation
0
No errors.
1
Device guarding failed after device
was operational.
Device
Check if device is still running.
30
Device access timeout.
Device
Device does not respond. Check
the baud rate and MAC ID.
32
Device rejects access with unknown
error code.
Device
Use single-device diagnostic to
get reject code.
35
Device response in allocation phase
with connection error.
Device
Use single-device diagnostic to
get additional reject code.
36
Connection produced (process data
input length from the FMU's
point-of-view) is different from the one
configured.
Device/configuration Use
single-device diagnostic to
get true produced connection
size.
37
Size of connection consumed
(process data output length from the
FMU's point-of-view) is different from
the one configured.
Device/configuration Use
single-device diagnostic to
get true consumed connection
size.
38
Device service response telegram
unknown and not handled.
Device/configuration Use
single-device diagnostic to
get true consumed connection
size.
39
Connection already requested.
Device
Connection will be automatically
released.
40
Number of CAN message data bytes
read in the produced or consumed
connection size response unequal to
4.
Device
Device cannot operate with the
FMU and norm description.
41
Predefined master-slave connection
already exits.
Device/FMU
Connection will be automatically
released.
42
Length in polling device response
unequal to produced connection size.
Device
43
Sequence error in device polling
response.
Device
Two initial segments in
multiplexed transfer were
received.
44
Fragment error in device polling
response.
Device
Fragmentation counter during
multiplexed transfer differs from
the one expected.
45
Sequence error in device polling
response.
Device
Middle or last segment was
received before the first
segment.
46
Length in bit strobe device response
unequal to produced connection size.
Device
47
Sequence error in device COS or
cyclic response.
Device
Two initial segments in
multiplexed transfer were
received.
48
Fragment error in device COS or
cyclic response.
Device
Fragmentation counter during
multiplexed transfer differs from
the one expected.
49
Sequence error in device COS or
cyclic response.
Device
Middle or last segment was
received before the first
segment.
Содержание FMU
Страница 1: ...programmable logic controller FMU Technical Manual ...
Страница 3: ......
Страница 9: ......
Страница 10: ...Chapter 1 Features and Restrictions ...
Страница 13: ......
Страница 14: ...Chapter 2 Parts and Functions ...
Страница 23: ......
Страница 24: ...Chapter 3 Specifications ...
Страница 30: ...Chapter 4 Installation and Wiring ...
Страница 42: ...Chapter 5 Programming Information for Control FPWIN Pro ...
Страница 70: ...Chapter 6 Outline Dimensions ...
Страница 73: ......
Страница 76: ...Record of Changes Manual No Date Description of changes ACGM0161V10EN July 2008 First edition ...