Programming Information for Control FPWIN Pro
FMU Technical Manual
42
Global bits
The bit field serves as collective display of global notifications. Errors can either occur at the
FMU itself or at the slaves. To distinguish between the different errors, the variable part
ErrRemAddr contains the error location (address = MAC ID), while the variable part ErrEvent
lists the corresponding error number. If more than one error is detected, the error location will
always show the device with the lowest MAC ID.
Bit:
0
7
6
5
4
3
2
1
Bit
Explanation
0
Control error
. Parameterization error.
1
Auto-clear error
. FMU stopped communication to all slaves and reached the auto-clear end state.
2
Non-exchange error
. At least one slave has not reached the data exchange state, hence no process
data can be exchanged.
3
Fatal error
. Due to severe bus error, no further bus communication is possible.
4
Event error
. The FMU has detected bus short circuits. The number of detected events are fixed in the
BusErrorCnt variable. The bit is set when the first event is detected.
5
Host not ready notification
. If the bit is set, the host program ist NOT ready to communicate.
6
Duplicate MAC ID detected
. The FMU has detected another device in the network with the same
MAC ID.
7
Duplicate MAC ID check in progress
. As long this bit is set, the FMU is checking for duplicate MAC
IDs.
Errors
The following error numbers are valid for the error event if "Error remote address" is 255.
ErrEvent
Explanation
Source of error
Recommendation
52
Unknown process data handshake
mode configured.
Configuration.
53
Baud rate out of range.
Configuration.
54
FMU MAC ID address out of range.
Configuration.
57
Duplicate FMU MAC ID address
detected in the network
Configuration or
network.
58
No device entry found in the current
configuration database.
Download error in
the current
database.
Contact technical support.
210
No database found in the system.
Configuration not
downloaded. FMU
is not configured by
Control Configurator
FM.
212
Failure reading the database.
Contact technical support.
220
User watchdog failed.
Application.
221
No data acknowledgement from user.
Application.
223
Master has stopped bus
communication due to CAN-based bus
off error. In the Control Configurator FM
for the bus parameters under "Error
handling", "Auto Clear" is activated.
Network error.
226
Master firmware downloaded to slave
EC1 device.
User error.
Содержание FMU
Страница 1: ...programmable logic controller FMU Technical Manual ...
Страница 3: ......
Страница 9: ......
Страница 10: ...Chapter 1 Features and Restrictions ...
Страница 13: ......
Страница 14: ...Chapter 2 Parts and Functions ...
Страница 23: ......
Страница 24: ...Chapter 3 Specifications ...
Страница 30: ...Chapter 4 Installation and Wiring ...
Страница 42: ...Chapter 5 Programming Information for Control FPWIN Pro ...
Страница 70: ...Chapter 6 Outline Dimensions ...
Страница 73: ......
Страница 76: ...Record of Changes Manual No Date Description of changes ACGM0161V10EN July 2008 First edition ...