14.2. Relationship Between The Condition Of The Air Conditioner And
Pressure And Electric Current
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
14.3. Diagnosis Methods Of A Malfunction Of A Compressor And 4-way Valve
Cooling Mode
Heating Mode
Condition of the
air conditoner
Low Pressure
High Pressure
Electric current
during operation
Low Pressure
High Pressure
Electric current
during operation
Insufficient refrigerant
(gas leakage)
Clogged capillary tube or
Strainer
Short circuit in the indoor unit
Heat radiation deficiency of
the outdoor unit
Inefficient compression
Nature of fault
Symptom
• Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor
• The discharge tube of the compressor becomes abnormally hot (normally 70 to 90
°
C).
• The difference between high pressure and low pressure becomes almost zero.
Locked compressor
• Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
• The compressor has a humming sound.
Insufficient switches of the 4-way valve
• Electric current during operation becomes approximately 80% lower than the normal value.
• The temperature different between from the discharge tube to the 4-way valve and from
suction tube to the 4-way valve becomes almost zero.
Содержание CS-YW9GKE
Страница 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS YW9GK CS YW12GK...
Страница 11: ...11 5 2 Outdoor Unit 5 2 1 CU YW9GK CU YW12GK...
Страница 12: ...12 6 Refrigeration Cycle Diagram...
Страница 13: ...13 7 Block Diagram...
Страница 15: ...15 9 Electronic Circuit Diagram...
Страница 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit Main Printed Circuit Board...
Страница 17: ...17 10 2 Indoor Unit Power Printed Circuit Board...
Страница 18: ...18 10 3 Indicator TOP VIEW BOTTOM VIEW...
Страница 21: ...21 3 For the embedded piping This can be used for left rear piping and left bottom piping also...
Страница 33: ...33 Normal Deicing Time Diagram Overload Deicing Time Diagram...
Страница 43: ...43...
Страница 44: ...44 15 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures...
Страница 45: ...45...
Страница 46: ...46 16 Technical Data 16 1 Thermostat Characteristics Cooling Soft Dry Heating...
Страница 48: ...48 16 3 Operation Characteristics 16 3 1 CS YW9GK CU YW9GK...
Страница 49: ...49...
Страница 50: ...50...
Страница 51: ...51...
Страница 52: ...52 16 3 2 CS YW12GK CU YW12GK...
Страница 53: ...53...
Страница 54: ...54...
Страница 55: ...55...