12.5.10. 30 Minutes Time Save Control
• The compressor will start automatically if it has stopped for 30 minutes and the intake air temperature falls between the
compressor OFF temperature (A) and compressor ON temperature (B) during the period.
• This is maintain the room temperature as set. Despite of this, it is to prevent a wrong judgement of intake air temperature due to
poor installation near the sensor area.
12.5.11. Overload Protection Control
• Outdoor Fan Control
- If the temperature of the indoor heat exchanger rises to 51°C, outdoor fan stops. The outdoor fan restarts when the indoor
heat exchanger temperature falls to 49°C.
• Compressor high pressure protection
- If the indoor heat exchanger becomes 65° C or more, the compressor will stop and restart automatically.
(Time Delay Safety Control - 4 minutes waiting).
- This is to reduce the pressure, as to reduce the indoor heat exchanger temp. Nevertheless, is to protect the compressor from
overload of too high temperature.
12.5.12. 4-Way Valve Control
• 4-way valve always on during Heating operation. (except deicing operation)
• When the unit is switched off by remote control during Heating operation, the 4-way valve stay at Heating position for 5 minutes.
• This is to prevent the refrigerant flow process sound for being occur.
12.5.13. Outdoor Fan Motor Control
• When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds (forced operation).
• This is to release the heat and to obtain the lowest pressure as fast as possible.
12.5.14. Hot Start Control
• Hot Start Control is to prevent cool air discharge into the room when heating operation start.
• When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
• Hot start is completed when indoor heat exchanger rises to 39°C or operation over 4 minutes.
Содержание CS-YW9GKE
Страница 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS YW9GK CS YW12GK...
Страница 11: ...11 5 2 Outdoor Unit 5 2 1 CU YW9GK CU YW12GK...
Страница 12: ...12 6 Refrigeration Cycle Diagram...
Страница 13: ...13 7 Block Diagram...
Страница 15: ...15 9 Electronic Circuit Diagram...
Страница 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit Main Printed Circuit Board...
Страница 17: ...17 10 2 Indoor Unit Power Printed Circuit Board...
Страница 18: ...18 10 3 Indicator TOP VIEW BOTTOM VIEW...
Страница 21: ...21 3 For the embedded piping This can be used for left rear piping and left bottom piping also...
Страница 33: ...33 Normal Deicing Time Diagram Overload Deicing Time Diagram...
Страница 43: ...43...
Страница 44: ...44 15 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures...
Страница 45: ...45...
Страница 46: ...46 16 Technical Data 16 1 Thermostat Characteristics Cooling Soft Dry Heating...
Страница 48: ...48 16 3 Operation Characteristics 16 3 1 CS YW9GK CU YW9GK...
Страница 49: ...49...
Страница 50: ...50...
Страница 51: ...51...
Страница 52: ...52 16 3 2 CS YW12GK CU YW12GK...
Страница 53: ...53...
Страница 54: ...54...
Страница 55: ...55...