15.2. Breakdown Self Diagnosis Function
15.2.1.
Self Diagnosis Function (Three Digits Alphanumeric Code)
• Once abnormality has been detected during operation, the
unit will immediately stop its operation. (Timer LED blinks.)
• Although timer LED goes off when power supply is turned
off, if the unit is operated under a breakdown condition, the
LED will light up again.
• In operation after breakdown repair, error code is not
displayed. The last error code (abnormality) will be saved in
IC memory.
•
Timer LED Blinking in Abnormal Operation:
1. Automatically stops the operation.
2. Timer LED on display of the indoor unit blinks.
3. The LED will be off if the unit is turned off or the Error
RESET button on the remote controller is pressed.
•
To display memorized error (Protective operation)
status:
1. Turn the unit on.
2. Slide the remote controller cover down to show the
operating buttons.
3. Press the CHECK button on the remote controller for
continuously 5 seconds or more to show “--” on the
display.
4. Press the “TEMP” or button on the remote controller
to show “H00” on the display. Signal is transmitted to the
main unit.
5. Press the “TEMP” or button (When button is
pressed, the display goes back.) repeatedly and slowly
until Beep sound (about 5 seconds intermittently) is heard
from main unit.
6. Then, displayed error code matches to the error code
saved in unit memory. The power LED on the main unit
also lights up.
Note: When the CHECK button is pressed
continuously for 5 seconds again, or when no
operation continues for 30 seconds, or when the
RESET button on remote controller is pressed with a
pointed object, the display is cancelled.
•
To clear memorized error (Protective operation) status
after repair:
1. Press the AUTO button in main unit continuously for 5
seconds or more and release it. (Test run / Pump down
operation: Beep sound).
2. Press the CHECK button on remote controller for about 1
second to transmit signal to main unit. A beep sound is
heard from main unit and the data is cleared..
•
Temporary Operation (Depending on breakdown status)
1. Press the ON/OFF button after selecting Cooling or
Heating operation. (Receiving Beep sound is heard and
the TIMER LED blinks.)
2. The unit can temporarily be used until repaired.
Error Code
Operation
Temporary items
H23
Cooling
Emergency Operation
with limited power
H27, H28
Cooling, Heating
Содержание CS-TE15HKE
Страница 8: ...8 5 Dimensions 5 1 Indoor Unit...
Страница 9: ...9 5 2 Outdoor Unit...
Страница 10: ...10 6 Refrigeration Cycle Diagram...
Страница 11: ...11 7 Block Diagram...
Страница 12: ...12 8 Wiring Connection Diagram 8 1 Indoor Unit...
Страница 13: ...13 8 2 Outdoor Unit...
Страница 14: ...14 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Страница 15: ...15 9 2 Outdoor Unit...
Страница 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Printed Circuit Board...
Страница 17: ...17 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board...
Страница 20: ...20 3 For the embedded piping This can be used for left rear piping and left bottom piping also...
Страница 43: ...43 16 1 2 Removal of Electronic Controller...
Страница 44: ...44 16 1 3 Removal of Control Board...
Страница 45: ...45 16 1 4 Removal of Fan Motor and Cross Flow Fan...
Страница 46: ...46...
Страница 48: ...48 17 Technical Data 17 1 Operation Characteristics...
Страница 49: ...49...
Страница 50: ...50...
Страница 51: ...51...