13.3. Protection Control For Heating Operation
13.3.1.
Intake Air Temperature Control
Compressor will operate at Max freq. if either one of the below conditions occur:
1. When the indoor intake air temperature is 30
q
C or above.
13.3.2.
Outdoor Air Temperature Control
• The Max current value is regulated when the outdoor air temperature rise above 14
q
C in order to avoid compressor overloading.
13.3.3.
Overload Protection Control
• The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below.
• If the heat exchanger temperature exceeds 60
q
C, compressor will stopped.
Содержание CS-TE15HKE
Страница 8: ...8 5 Dimensions 5 1 Indoor Unit...
Страница 9: ...9 5 2 Outdoor Unit...
Страница 10: ...10 6 Refrigeration Cycle Diagram...
Страница 11: ...11 7 Block Diagram...
Страница 12: ...12 8 Wiring Connection Diagram 8 1 Indoor Unit...
Страница 13: ...13 8 2 Outdoor Unit...
Страница 14: ...14 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Страница 15: ...15 9 2 Outdoor Unit...
Страница 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Printed Circuit Board...
Страница 17: ...17 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board...
Страница 20: ...20 3 For the embedded piping This can be used for left rear piping and left bottom piping also...
Страница 43: ...43 16 1 2 Removal of Electronic Controller...
Страница 44: ...44 16 1 3 Removal of Control Board...
Страница 45: ...45 16 1 4 Removal of Fan Motor and Cross Flow Fan...
Страница 46: ...46...
Страница 48: ...48 17 Technical Data 17 1 Operation Characteristics...
Страница 49: ...49...
Страница 50: ...50...
Страница 51: ...51...