14.4.17 F91 (Refrigeration Cycle Abnormality)
Malfunction Decision Conditions
•
During cooling, compressor frequency = Fcmax.
•
During cooling and heating operation, running current: 0.65A < I < 1.65A.
•
During cooling, indoor intake - indoor pipe < 4°C.
Malfunction Caused
•
Refrigerant shortage (refrigerant leakage)
•
Poor compression performance of compressor.
•
2/3 way valve closed.
•
Detection error due to faulty indoor intake air or indoor pipe temperature sensors.
Troubleshooting