10.2.1 Connect the Cable to the Indoor Unit
1 The inside and outside connection cable can
be connected without removing the front grille.
2
Connection cable
between indoor unit and
outdoor unit shall be approved
polychloroprene sheathed 4 x 1.5 mm
2
(1.0 ~
1.5HP) or 4 x 2.5 mm
2
(2.0 ~ 2.5HP) flexible
cord, type designation 245 IEC 57 or heavier
cord. Do not use joint connection cable.
Replace the wire if the existing wire (from
concealed wiring, or otherwise) is too short.
•
Secure the connection cable onto the control
board with the holder.
Note:
•
Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
•
Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
•
Earth wire shall be Yellow/Green (Y/G) in colour and longer than other AC wires as shown in the figure for the
electrical safety in case of the slipping out of the cord from the anchorage.
Содержание CS-S9NKV
Страница 15: ...15 4 2 3 CU S18NKV CU S24NKV...
Страница 16: ...16 4 2 4 CU S28NKV...
Страница 17: ...17 5 Refrigeration Cycle Diagram 5 1 CS S9NKV CU S9NKV CS S12NKV CU S12NKV...
Страница 18: ...18 5 2 CS S18NKV CU S18NKV CS S24NKV CU S24NKV...
Страница 19: ...19 5 3 CS S28NKV CU S28NKV...
Страница 24: ...24 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS S9NKV CS S12NKV...
Страница 25: ...25 7 1 2 CS S18NKV CS S24NKV...
Страница 26: ...26 7 1 3 CS S28NKV...
Страница 31: ...31 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS S9NKV CS S12NKV...
Страница 32: ...32 8 1 2 CS S18NKV CS S24NKV...
Страница 33: ...33 8 1 3 CS S28NKV...
Страница 41: ...41 9 1 5 Human Activity Sensor Printed Circuit Board...
Страница 42: ...42 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9NK...
Страница 43: ...43 9 2 1 2 CU S12NK...
Страница 44: ...44 9 2 1 3 CU S18NK CU S24NK...
Страница 45: ...45 9 2 1 4 CU S28NK...
Страница 46: ...46 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU S9NKV...
Страница 47: ...47 9 2 2 2 CU S28NKV...