12.5 Low Pressure Prevention Control (Gas Leakage Detection)
•
Control start conditions
o
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o
During Cooling and Soft Dry operation:
Indoor suction temperature – indoor piping temperature is below 4°C
•
Control
contents
o
Compressor stops (and restart after 3 minutes).
o
If the conditions above happened 2 times within 20 minutes, the unit will:
Stop
operation
Timer LED blinks and “F91” indicated.
12.6 Compressor Tank Temperature Rise Protection Control
•
Control start conditions
o
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.65A and 1.65A.
o
During Cooling and Soft Dry operation:
Indoor suction temperature -indoor piping temperature is below 4°C.
Indoor temperature and outdoor temperature is 30±5°C.
Remote Control setting 16°C and Hi Fan Speed.
•
Control
contents
o
Compressor stops (and restart after 3 minutes)
o
If the conditions above happened 2 times within 20 minutes, the unit will:
Stop
operation
Timer LED blinks and “F91” indicated.
12.7 Low Frequency Protection Control 1
•
When the compressor operates at frequency lower than 24Hz continued for 20 minutes, the operation frequency
will be changed to 23Hz for 2 minutes.
12.8 Low Frequency Protection Control 2
•
When all below conditions comply, the compressor frequency will changed to lower frequency.
Temperature, T, for:
Cooling / Soft Dry
Indoor intake air (°C)
T < 15 or T
≥
30
Outdoor air (°C)
T < 16 or T
≥
38
Indoor heat exchanger (°C)
T < 30
12.9 Outdoor Air Temperature Control
•
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
•
This control will begin 1 minute after the compressor starts.
•
Compressor
frequency will adjust based on outdoor air temperature.
Free
Limited Frequency
Outdoor air temperature
38°C
37°C
Содержание CS-PS9PKV
Страница 9: ...9 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Страница 10: ...10 4 Dimensions 4 1 Indoor Unit 4 1 1 CS PS9PKV CS PS12PKV...
Страница 11: ...11 4 1 2 CS PS18PKV CS PS24PKV...
Страница 12: ...12 4 2 Outdoor Unit 4 2 1 CU PS9PKV 4 2 2 CU PS12PKV CU PS18PKV...
Страница 13: ...13 4 2 3 CU PS24PKV...
Страница 14: ...14 5 Refrigeration Cycle Diagram 5 1 CS PS9PKV CU PS9PKV CS PS12PKV CU PS12PKV...
Страница 15: ...15 5 2 CS PS18PKV CU PS18PKV CS PS24PKV CU PS24PKV...
Страница 16: ...16 6 Block Diagram 6 1 CS PS9PKV CU PS9PKV...
Страница 17: ...17 6 2 CS PS12PKV CU PS12PKV...
Страница 18: ...18 6 3 CS PS18PKV CU PS18PKV...
Страница 19: ...19 6 4 CS PS24PKV CU PS24PKV...
Страница 21: ...21 7 1 2 CS PS18PKV CS PS24PKV...
Страница 26: ...26 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS PS9PKV CS PS12PKV...
Страница 27: ...27 8 1 2 CS PS18PKV CS PS24PKV...
Страница 28: ...28 8 2 Outdoor Unit 8 2 1 CU PS9PKV...
Страница 29: ...29 8 2 2 CU PS12PKV...
Страница 30: ...30 8 2 3 CU PS18PKV...
Страница 31: ...31 8 2 4 CU PS24PKV...
Страница 32: ...32 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board 9 1 1 1 CS PS9PKV CS PS12PKV...
Страница 33: ...33 9 1 1 2 CS PS18PKV CS PS24PKV 9 1 2 Indicator and Receiver Printed Circuit Board...
Страница 34: ...34 9 1 3 Comparator Printed Circuit Board 9 1 4 Human Activity Sensor Printed Circuit Board...
Страница 35: ...35 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU PS9PKV...
Страница 36: ...36 9 2 1 2 CU PS12PKV...
Страница 37: ...37 9 2 1 3 CU PS18PKV...
Страница 38: ...38 9 2 1 4 CU PS24PKV...
Страница 39: ...39 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU PS9PKV...
Страница 92: ...92 Figure 13 Figure 14 15 2 3 To remove discharge grille Figure 15 15 2 4 To remove control board Figure 16...
Страница 93: ...93 15 2 5 To remove cross flow fan and indoor fan motor Figure 17 Figure 18 Figure 19...
Страница 94: ...94 Figure 20...