64
14.3 Error Code Table
Diagnosis
display
Abnormality / Protection control
Abnormality Judgment
Emergency
Operation
Primary location to verify
H00
No abnormality detected
-
Normal operation
H11
Indoor / Outdoor abnormal
communication
> 1 min after starting
operation
Indoor fan operation
only
•
Internal / external cable connection
•
Indoor / outdoor PCB
H12
Connection capability rank abnormality
Continuously for 90 sec
after power supplied
- -
H14
Indoor intake air temperature sensor
abnormality
Continue for 5 sec.
-
•
Intake air temperature sensor
(defective or disconnected)
H15
Outdoor compressor temperature sensor
abnormality
Continue for 5 sec.
-
•
Compressor temperature sensor
(defective or disconnected)
H16
Outdoor current transformer open circuit
-
-
•
Outdoor
PCB
•
IPM (Power transistor) module
H19
Indoor fan motor mechanism locked
7 occurrences
continuously
-
•
Indoor
PCB
•
Fan
motor
H23
Indoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
○
•
Heat exchanger temperature sensor
(defective or disconnected)
H27
Outdoor air temperature sensor
abnormality
Continue for 5 sec.
○
•
Outdoor temperature sensor
(defective or disconnected)
H28
Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
○
•
Outdoor heat exchanger
temperature sensor (defective or
disconnected)
H30
Outdoor discharge pipe temperature
sensor abnormality
Continue for 5 sec.
○
•
Outdoor discharge pipe temperature
sensor (defective or disconnected)
H33
Indoor / outdoor wrong connection
-
-
•
Indoor / outdoor supply voltage
H38
Indoor / outdoor mismatch (brand code)
-
-
-
H59
ECONAVI sensor abnormality
Continue for 25 sec.
-
•
ECONAVI sensor (defective or
disconnected)
•
ECONAVI
PCB
H97
Outdoor fan motor mechanism locked
2 occurrences within
30 minutes
-
•
Outdoor
PCB
•
Outdoor Fan Motor
H98
Indoor temperature rise abnormality
-
-
•
Air filter dirty
•
Air circulation short circuit
H99
Indoor heat exchanger freeze prevention
protection
- -
•
Insufficient
refrigerant
•
Air filter dirty
F11
4 way valve switching failure *
4 occurrences within
30 minutes
-
•
4-way
valve
•
v-coil
F90
System and compressor microcomputer
communication error(for S10*** only)
2 occurrences within
5 seconds
-
•
Compressor
•
Outdoor
PCB
F90
Power factor correction abnormality
4 occurrences within
20 minutes
-
•
Outdoor
PCB
F91
Refrigerant cycle abnormal
2 occurrences within
20 minutes
-
•
No refrigerant ( 3-way valve is
closed)
F93
Outdoor compressor abnormal revolution
4 occurrences within
20 minutes
-
•
Outdoor
compressor
F95
Cooling high pressure protection
4 occurrences within
20 minutes
-
•
Outdoor refrigerant circuit
F96
Intelligent power transistor overheating
protection
-
•
Excess
refrigerant
•
Improper heat radiation
•
IPM (Power transistor)
F97
Compressor temperature rise protection
control
4 times occurrence within
20 minutes
-
•
Insufficient
refrigerant
•
Compressor
F98
Total running current protection
3 times occurrence within
20 minutes
-
•
Excess
refrigerant
•
Improper heat radiation
F99
Outdoor direct current (DC) peak
detection
7 times occurrence
continuously
-
•
Outdoor
PCB
•
IPM (Power transistor)
•
Compressor
Note:
“
○
” – Frequency measured and fan speed fixed
“ * ”– For cooling only model, it is the indication when indoor heat exchanger sensor or indoor air intake sensor has
abnormality.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep”
sound heard following by pressing the CHECK button at remote control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors
(refer to Error Code Table) by using remote control or Auto OFF/ON button at indoor unit. However, the remote
control signal receiving sound is changed from one “beep” to four “beep” sounds.
Содержание CS-PS9PKV
Страница 9: ...9 3 Location of Controls and Components 3 1 Indoor Unit 3 2 Outdoor Unit 3 3 Remote Control...
Страница 10: ...10 4 Dimensions 4 1 Indoor Unit 4 1 1 CS PS9PKV CS PS12PKV...
Страница 11: ...11 4 1 2 CS PS18PKV CS PS24PKV...
Страница 12: ...12 4 2 Outdoor Unit 4 2 1 CU PS9PKV 4 2 2 CU PS12PKV CU PS18PKV...
Страница 13: ...13 4 2 3 CU PS24PKV...
Страница 14: ...14 5 Refrigeration Cycle Diagram 5 1 CS PS9PKV CU PS9PKV CS PS12PKV CU PS12PKV...
Страница 15: ...15 5 2 CS PS18PKV CU PS18PKV CS PS24PKV CU PS24PKV...
Страница 16: ...16 6 Block Diagram 6 1 CS PS9PKV CU PS9PKV...
Страница 17: ...17 6 2 CS PS12PKV CU PS12PKV...
Страница 18: ...18 6 3 CS PS18PKV CU PS18PKV...
Страница 19: ...19 6 4 CS PS24PKV CU PS24PKV...
Страница 21: ...21 7 1 2 CS PS18PKV CS PS24PKV...
Страница 26: ...26 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS PS9PKV CS PS12PKV...
Страница 27: ...27 8 1 2 CS PS18PKV CS PS24PKV...
Страница 28: ...28 8 2 Outdoor Unit 8 2 1 CU PS9PKV...
Страница 29: ...29 8 2 2 CU PS12PKV...
Страница 30: ...30 8 2 3 CU PS18PKV...
Страница 31: ...31 8 2 4 CU PS24PKV...
Страница 32: ...32 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board 9 1 1 1 CS PS9PKV CS PS12PKV...
Страница 33: ...33 9 1 1 2 CS PS18PKV CS PS24PKV 9 1 2 Indicator and Receiver Printed Circuit Board...
Страница 34: ...34 9 1 3 Comparator Printed Circuit Board 9 1 4 Human Activity Sensor Printed Circuit Board...
Страница 35: ...35 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU PS9PKV...
Страница 36: ...36 9 2 1 2 CU PS12PKV...
Страница 37: ...37 9 2 1 3 CU PS18PKV...
Страница 38: ...38 9 2 1 4 CU PS24PKV...
Страница 39: ...39 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU PS9PKV...
Страница 92: ...92 Figure 13 Figure 14 15 2 3 To remove discharge grille Figure 15 15 2 4 To remove control board Figure 16...
Страница 93: ...93 15 2 5 To remove cross flow fan and indoor fan motor Figure 17 Figure 18 Figure 19...
Страница 94: ...94 Figure 20...