14.5.23 F99 (Output Over Current Detection)
Malfunction Decision Conditions
During operation of cooling and heating, when an output over-current (20.2A) is detected by checking the current
that flows in the inverter DC peak sensing circuitry.
Malfunction Caused
DC peak due to compressor failure.
DC peak due to defective power transistor(s).
DC peak due to defective outdoor unit PCB.
Troubleshooting
Checking the power transistor
Never touch any live parts for at least 10 minutes after turning off the circuit breaker.
If unavoidable necessary to touch a live part, make sure the power transistor’s supply voltage is below 50V using
the tester.
For the UVW, make measurement at the Faston terminal on the board of the relay connector.
Tester’s negative terminal
Power transistor (+)
UVW
Power transistor (-)
UVW
Tester’s positive terminal
UVW
Power transistor (+)
UVW
Power transistor (-)
Normal resistance
Several k
Ω
to several M
Ω
Abnormal resistance
0 or
∞
Содержание CS-ME9PB4EA
Страница 28: ...28 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Страница 29: ...29 5 Dimensions 5 1 Indoor Unit...
Страница 30: ...30 6 Refrigeration Cycle Diagram...
Страница 31: ...31 7 Block Diagram...
Страница 32: ...32 8 Wiring Connection Diagram 8 1 Indoor Unit...
Страница 33: ...33 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Страница 34: ...34 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Страница 80: ...80 8 Remove the Fan Motor by release the Fan Motor lead wire connectors and Fan Motor screws Fig 8 Fig 8...
Страница 81: ...81 16 Exploded View and Replacement Parts List 16 1 Indoor Unit...