75
14.5.21 F97 (Compressor Overheating)
Malfunction Decision Conditions
During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the
compressor tank temperature sensor.
Malfunction Caused
Refrigerant shortage (refrigerant leakage).
2/3 way valve closed.
Detection error due to faulty compressor tank temperature sensor.
Troubleshooting
Содержание CS-ME9PB4EA
Страница 28: ...28 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Страница 29: ...29 5 Dimensions 5 1 Indoor Unit...
Страница 30: ...30 6 Refrigeration Cycle Diagram...
Страница 31: ...31 7 Block Diagram...
Страница 32: ...32 8 Wiring Connection Diagram 8 1 Indoor Unit...
Страница 33: ...33 9 Electronic Circuit Diagram 9 1 Indoor Unit...
Страница 34: ...34 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Страница 80: ...80 8 Remove the Fan Motor by release the Fan Motor lead wire connectors and Fan Motor screws Fig 8 Fig 8...
Страница 81: ...81 16 Exploded View and Replacement Parts List 16 1 Indoor Unit...