2

IMPORTANT! 
Please Read Before Starting

This air conditioning system meets strict safety and operating
standards. As the installer or service person, it is an important
part of your job to install or service the system so it operates
safely and efficiently. 

For safe installation and trouble-free operation, you
must:

Carefully read this instruction booklet before beginning.

Follow each installation or repair step exactly as shown.

Observe all local, state, and national electrical codes.

Pay close attention to all warning and caution notices
given in this manual.

This symbol refers to a hazard
or unsafe practice which can
result in severe personal injury
or death.

This symbol refers to a hazard
or unsafe practice which can
result in personal injury or prod-
uct or property damage.

If Necessary, Get Help

These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions. 

In Case of Improper Installation

The manufacturer shall in no way be responsible for improp-
er installation or maintenance service, including failure to
follow the instructions in this document. 

SPECIAL PRECAUTIONS

When Wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A
QUALIFIED, EXPERIENCED ELECTRICIAN
SHOULD ATTEMPT TO WIRE THIS SYSTEM. 

‡ 'RQRWVXSSO\SRZHUWRWKHXQLWXQWLODOOZLULQJDQGWXELQJ

are completed or reconnected and checked.

‡ +LJKO\GDQJHURXVHOHFWULFDOYROWDJHVDUHXVHGLQWKLV

system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause 

accidental injury or

death.

‡ *URXQGWKHXQLW

following local electrical codes.

‡ &RQQHFWDOOZLULQJWLJKWO\/RRVHZLULQJPD\FDXVHRYHU

heating at connection points and a possible fire hazard.

‡ 7RSUHYHQWSRVVLEOHKD]DUGVIURPLQVXODWLRQIDLOXUH

the unit must be grounded.

When Transporting

Be careful when picking up and moving the indoor and out-
door units. Get a partner to help, and bend your knees when
lifting to reduce strain on your back. Sharp edges or thin alu-
minum fins on the air conditioner can cut your fingers. 

When Installing…

Select an installation location which is rigid and strong
enough to support or hold the unit, and select a location for
easy maintenance.

…In a Ceiling or Wall

Make sure the ceiling/wall is strong enough to hold the
unit’s weight. It may be necessary to construct a strong
wood or metal frame to provide added support.

…In a Room

Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.

Keep the fire alarm and the air
outlet at least 1.5 m away from
the unit.

When Connecting Refrigerant Tubing

‡ 9HQWLODWHWKHURRPZHOOLQWKHHYHQWWKDWUHIULJHUDQW

gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.

‡ 'RQRWDGGDQ\UHIULJHUDQWDLURUVXEVWDQFHLQWRWKH

refrigeration circuit other than the designated refrigerant
(R410A). Adding anything other than the specified refrig-
erant may cause the pressure to rise excessively in the
refrigeration circuit, rupturing the circuit and causing injury
or damage.

‡ 8VHDOOQHZWXELQJDQGIODUHQXWVWRPDNHWKHWXELQJFRQ

nections. Using any previous parts (from R22-based sys-
tems) may result in damage to the equipment, and may
lead to the refrigeration circuit rupturing, causing a seri-
ous accident.

WARNING

WARNING

CAUTION

CAUTION

WARNING

‡ :KHQSHUIRUPLQJ

piping work

do not mix air except for speci-
fied refrigerant (R410A) in
refrigeration cycle. It causes
capacity down, and risk of
explosion and injury due to
high tension inside the refrige-
rant cycle.

‡ 5HIULJHUDQWJDVOHDNDJHPD\

cause fire.

‡ 'RQRWDGGRUUHSODFHUHIULJHUDQW

other than specified type.
It may cause product damage,
burst and injury etc.

Содержание CS-KS18NB4UW & CZ-18BT1U + CU-KS18NKU

Страница 1: ...A 3 INSTALLATION INSTRUCTIONS CS MKS9NB4U CZ 18BT1U CS MKS12NB4U CZ 18BT1U CS KS18NB4UW CZ 18BT1U APPENDIX C 852 6 4190 582 00 0 ...

Страница 2: ... THE INDOOR UNIT 7 3 1 Preparation for Suspending 3 2 Suspending the Indoor Unit 3 3 Placing the Unit Inside the Ceiling 3 4 Installing the Drain Piping 3 5 Checking the Drainage 3 6 How to Install the Ceiling Panel 3 7 Wiring Instructions 3 8 Wiring Instructions for Inter unit Connections 4 HOW TO TEST RUN THE AIR CONDITIONER 14 5 REMOTE CONTROLLER INSTALLATION POSITION 15 5 1 Mounting on a Wall ...

Страница 3: ...azard 7R SUHYHQW SRVVLEOH KD DUGV IURP LQVXODWLRQ IDLOXUH the unit must be grounded When Transporting Be careful when picking up and moving the indoor and out door units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin alu minum fins on the air conditioner can cut your fingers When Installing Select an installation location which is rigid and...

Страница 4: ... ILQJHUV DQG FORWKLQJ DZD IURP DQ PRYLQJ parts OHDQ XS WKH VLWH DIWHU RX ILQLVK UHPHPEHULQJ WR FKHFN that no metal scraps or bits of wiring have been left inside the unit being serviced Others 9HQWLODWH DQ HQFORVHG DUHDV ZKHQ LQVWDOOLQJ RU WHVWLQJ the refrigeration system Escaped refrigerant gas on contact with fire or heat can produce dangerously toxic gas RQILUP XSRQ FRPSOHWLQJ LQVWDOODWLRQ WKDW...

Страница 5: ...nits and make sure all accessory parts listed are with the system before beginning 1 1 Tools Required for Installation not supplied 1 Standard screwdriver 2 Phillips head screwdriver 3 Knife or wire stripper 4 Tape measure 5 Carpenter s level 6 Sabre saw or key hole saw 7 Hacksaw 8 Core bits 9 Hammer 10 Drill 11 Tube cutter 12 Tube flaring tool 13 Torque wrench 14 Adjustable wrench 15 Reamer for d...

Страница 6: ...ition from which every corner of the room can be uniformly cooled select a location that will hold the weight of the unit select a location where tubing and drain hose have the shortest run to the outside allow room for operation and maintenance as well as unrestricted air flow around the unit Fig 1 install the unit within the maximum elevation difference H1 H2 H3 H4 above or below the outdoor uni...

Страница 7: ...ds securely If a tube is left open for an extended time moisture in the air inside the tubing may condense into water droplets and lead to water contamination of the refrig erant circuit In order to prevent insulation breakdown and ground faults do not allow wiring ends to come in contact with rainwater or be subjected to condensation or dew Apply sufficient thermal insulation to the refrigerant t...

Страница 8: ...ram The dia gram shows the relationship between the positions of the suspension fitting unit and panel Fig 6 2 3 3 Placing the Unit Inside the Ceiling 1 Be sure to remove the fan protection 4pcs for transportation before hanging up the indoor unit 2 When placing the unit inside the ceiling determine the pitch of the suspension bolts using the supplied full scale installation diagram Fig 6 3 Tubing...

Страница 9: ...ll the drain hose first place 1 of the 2 hose bands over the unit drain port and the other hose band over the hard PVC pipe not supplied Then connect both ends of the supplied drain hose Fig 6 5 3 On the unit drain side grasp the hose band with pliers and insert the drain hose all the way to the base If other commercially available hose bands are used the drain hose may become pinched or wrinkled ...

Страница 10: ...nit position 1 Check that the ceiling hole is 23 5 8 600 mm 23 5 8 600 mm Fig 6 11 2 Confirm that the position of the indoor unit and the ceiling as shown in the diagram If the positions of the ceiling sur face and unit do not match air leakage water leakage flap operation failure or other problems may occur Fig 6 11 The drain pump will continue to operate for a minimum of 6 min utes after the FS ...

Страница 11: ... the unit and the ceiling panel or between the ceiling panel and the ceiling surface If there is a gap between the panel and the ceiling leave the ceiling panel attached and make fine adjustments to the installation height of the unit to eliminate the gap with the ceiling CAUTION Fig 6 17 Fig 6 18 Fig 6 19 Corner cover Indicator cover Press Pull up 2 1 latch Temporary latches Temporary DRAIN mark ...

Страница 12: ...ignal will not be received If the connectors are not connected the auto flap will not operate Be sure to connect them securely A Attaching the corner cover 1 Check that the safety strap from the corner cover is fas tened to the ceiling panel pin as shown in the figure Fig 6 23 2 Use the supplied screws to attach the corner cover to the ceiling panel B Attaching the air intake grille To install the...

Страница 13: ...used exclusively for each unit with a power supply disconnect and circuit breaker for overcurrent protection provided in the exclusive line 3 To prevent possible hazards due to insulation failure the unit must be grounded 4 Each wiring connection must be done tightly and in accordance with the wiring system diagram Wrong wiring may cause the unit to misoperate or become damaged 5 Do not allow wiri...

Страница 14: ... the terminal screw 4 Shape the loop wire properly place it on the termi nal plate and fix it securely with the removed termi nal screw using a screwdriver For stranded wiring 1 Cut the wire end with a cutting pliers then strip the insulation to expose the stranded wiring about 3 8 10 mm and tightly twist the wire ends Figs 30 and 31 2 Using a screwdriver remove the terminal screw s on the termina...

Страница 15: ...PLQXWHV WKH V VWHP VKLIWV LQWR FRROLQJ operation and cool air will start to be felt Cooling mode test run is unaffected by the room tempera ture 3 Press the ON OFF operation button of the remote controller again to stop the test run Fig 33 LQDOO SUHVV WKH 5HVHW EXWWRQ RI WKH UHPRWH controller to release it from Test Run mode to return to normal mode Fig 33 µ DQG R3 µ ZLOO GLVDSSHDU IURP WKH UHPRWH...

Страница 16: ...ere is an obstacle between the remote con troller and the air conditioner since a check signal is sent from the remote controller every 5 minutes 5 1 Mounting on a Wall Before mounting the remote controller press the ON OFF operation button at the mounting location to make sure that the air conditioner operates from that location The indoor unit should make a beeping sound to indicate that it has ...

Страница 17: ...Then SUHVV DQG KROG WKH 5HVHW EXWWRQ ZLWK D pointed object such as the tip of a pen After 5 VHFRQGV UHOHDVH WKH EXWWRQ ILUVW WKHQ release the HIGH POWER and 1HR TIMER but tons oP 1 Test Run appears blinking in the remote controller clock display area 4 Each time the 1HR TIMER button is pressed the display changes as shown below Press this but ton 2 times to change the display to oP 7 Address setti...

Страница 18: ...nstalled level and vertically The power and voltage are as specified Inter unit cables are securely inserted into the terminal block Inter unit cables are securely fixed The power cable and inter unit cables are not connected anywhere along their paths The ground wire is securely connected Thermal insulation has been applied to the tubing connections Drain connections are secure and water drains p...

Отзывы: