background image

12

3-6-5.  Checking After Installation

Check that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling sur-
face. Gaps may cause water leakage and condensation.

Check that the wiring is securely connected. 
If it is not securely connected, the auto flap will not operate. In addition, water leakage and condensation may occur.

3-6-6.  When Removing the Ceiling Panel for Servicing

When removing the ceiling panel for servicing, remove the air-intake grille and air filter, disconnect the flap and the indi-
cator wiring connectors inside the control box, and then remove the 4 mounting screws.

3-6-7.  Adjusting the Auto Flap

The air-direction flap on the ceiling panel outlet can be adjusted as follows.

Adjust the flap to the desired angle using the remote controller. The flap also has an automatic air-sweeping mecha-
nism.

Never attempt to move the flap by hand.

Proper air flow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or
heating seems inadequate, try changing the direction of the air flow.

3-7.  Wiring Instructions

General precautions on wiring

(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely fol-

lowing the wiring diagram.

(2) Provide a power outlet to be used exclusively for each unit, with a power supply disconnect and circuit breaker for

overcurrent protection provided in the exclusive line.

(3) To prevent possible hazards due to insulation failure, the unit must be grounded.

(4) Each wiring connection must be done tightly and in accordance with the wiring system diagram. Wrong wiring may

cause the unit to misoperate or become damaged.

(5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.

(6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility

for any damage or misoperation that occurs as a result of such unauthorized changes.

NOT

E

Fig. 8

1

3

2

Earth screw

Clamping strap

(Conduit)

Inter unit

Power wiring 
(Locally purchased)

3-8.  Wiring Instructions for Inter-unit Connections

(1) Remove the 1 screw from the terminal cover, then open the

cover. Be careful that the cover does not fall.

(2) Remove the 3 screws from the power box cover, then open

the cover. Be careful that the cover does not fall.

(3) Use the screw to securely fasten the ground wire from the

outdoor unit in place.

(4) Remove the transparent plastic cover from the 3P terminal

plate.

(5) While viewing the wiring diagram, connect the inter-unit and

power supply line to terminals 1, 2 and 3 on the 3P terminal
plate.

(6) Remount the transparent plastic cover onto the 3P terminal

plate.

(7) Be sure to use the clamping strap to fasten the wires in place.

(8) Tighten the screws to remount the terminal and the power

box cover.

Содержание CS-KS18NB4UW & CZ-18BT1U + CU-KS18NKU

Страница 1: ...A 3 INSTALLATION INSTRUCTIONS CS MKS9NB4U CZ 18BT1U CS MKS12NB4U CZ 18BT1U CS KS18NB4UW CZ 18BT1U APPENDIX C 852 6 4190 582 00 0 ...

Страница 2: ... THE INDOOR UNIT 7 3 1 Preparation for Suspending 3 2 Suspending the Indoor Unit 3 3 Placing the Unit Inside the Ceiling 3 4 Installing the Drain Piping 3 5 Checking the Drainage 3 6 How to Install the Ceiling Panel 3 7 Wiring Instructions 3 8 Wiring Instructions for Inter unit Connections 4 HOW TO TEST RUN THE AIR CONDITIONER 14 5 REMOTE CONTROLLER INSTALLATION POSITION 15 5 1 Mounting on a Wall ...

Страница 3: ...azard 7R SUHYHQW SRVVLEOH KD DUGV IURP LQVXODWLRQ IDLOXUH the unit must be grounded When Transporting Be careful when picking up and moving the indoor and out door units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin alu minum fins on the air conditioner can cut your fingers When Installing Select an installation location which is rigid and...

Страница 4: ... ILQJHUV DQG FORWKLQJ DZD IURP DQ PRYLQJ parts OHDQ XS WKH VLWH DIWHU RX ILQLVK UHPHPEHULQJ WR FKHFN that no metal scraps or bits of wiring have been left inside the unit being serviced Others 9HQWLODWH DQ HQFORVHG DUHDV ZKHQ LQVWDOOLQJ RU WHVWLQJ the refrigeration system Escaped refrigerant gas on contact with fire or heat can produce dangerously toxic gas RQILUP XSRQ FRPSOHWLQJ LQVWDOODWLRQ WKDW...

Страница 5: ...nits and make sure all accessory parts listed are with the system before beginning 1 1 Tools Required for Installation not supplied 1 Standard screwdriver 2 Phillips head screwdriver 3 Knife or wire stripper 4 Tape measure 5 Carpenter s level 6 Sabre saw or key hole saw 7 Hacksaw 8 Core bits 9 Hammer 10 Drill 11 Tube cutter 12 Tube flaring tool 13 Torque wrench 14 Adjustable wrench 15 Reamer for d...

Страница 6: ...ition from which every corner of the room can be uniformly cooled select a location that will hold the weight of the unit select a location where tubing and drain hose have the shortest run to the outside allow room for operation and maintenance as well as unrestricted air flow around the unit Fig 1 install the unit within the maximum elevation difference H1 H2 H3 H4 above or below the outdoor uni...

Страница 7: ...ds securely If a tube is left open for an extended time moisture in the air inside the tubing may condense into water droplets and lead to water contamination of the refrig erant circuit In order to prevent insulation breakdown and ground faults do not allow wiring ends to come in contact with rainwater or be subjected to condensation or dew Apply sufficient thermal insulation to the refrigerant t...

Страница 8: ...ram The dia gram shows the relationship between the positions of the suspension fitting unit and panel Fig 6 2 3 3 Placing the Unit Inside the Ceiling 1 Be sure to remove the fan protection 4pcs for transportation before hanging up the indoor unit 2 When placing the unit inside the ceiling determine the pitch of the suspension bolts using the supplied full scale installation diagram Fig 6 3 Tubing...

Страница 9: ...ll the drain hose first place 1 of the 2 hose bands over the unit drain port and the other hose band over the hard PVC pipe not supplied Then connect both ends of the supplied drain hose Fig 6 5 3 On the unit drain side grasp the hose band with pliers and insert the drain hose all the way to the base If other commercially available hose bands are used the drain hose may become pinched or wrinkled ...

Страница 10: ...nit position 1 Check that the ceiling hole is 23 5 8 600 mm 23 5 8 600 mm Fig 6 11 2 Confirm that the position of the indoor unit and the ceiling as shown in the diagram If the positions of the ceiling sur face and unit do not match air leakage water leakage flap operation failure or other problems may occur Fig 6 11 The drain pump will continue to operate for a minimum of 6 min utes after the FS ...

Страница 11: ... the unit and the ceiling panel or between the ceiling panel and the ceiling surface If there is a gap between the panel and the ceiling leave the ceiling panel attached and make fine adjustments to the installation height of the unit to eliminate the gap with the ceiling CAUTION Fig 6 17 Fig 6 18 Fig 6 19 Corner cover Indicator cover Press Pull up 2 1 latch Temporary latches Temporary DRAIN mark ...

Страница 12: ...ignal will not be received If the connectors are not connected the auto flap will not operate Be sure to connect them securely A Attaching the corner cover 1 Check that the safety strap from the corner cover is fas tened to the ceiling panel pin as shown in the figure Fig 6 23 2 Use the supplied screws to attach the corner cover to the ceiling panel B Attaching the air intake grille To install the...

Страница 13: ...used exclusively for each unit with a power supply disconnect and circuit breaker for overcurrent protection provided in the exclusive line 3 To prevent possible hazards due to insulation failure the unit must be grounded 4 Each wiring connection must be done tightly and in accordance with the wiring system diagram Wrong wiring may cause the unit to misoperate or become damaged 5 Do not allow wiri...

Страница 14: ... the terminal screw 4 Shape the loop wire properly place it on the termi nal plate and fix it securely with the removed termi nal screw using a screwdriver For stranded wiring 1 Cut the wire end with a cutting pliers then strip the insulation to expose the stranded wiring about 3 8 10 mm and tightly twist the wire ends Figs 30 and 31 2 Using a screwdriver remove the terminal screw s on the termina...

Страница 15: ...PLQXWHV WKH V VWHP VKLIWV LQWR FRROLQJ operation and cool air will start to be felt Cooling mode test run is unaffected by the room tempera ture 3 Press the ON OFF operation button of the remote controller again to stop the test run Fig 33 LQDOO SUHVV WKH 5HVHW EXWWRQ RI WKH UHPRWH controller to release it from Test Run mode to return to normal mode Fig 33 µ DQG R3 µ ZLOO GLVDSSHDU IURP WKH UHPRWH...

Страница 16: ...ere is an obstacle between the remote con troller and the air conditioner since a check signal is sent from the remote controller every 5 minutes 5 1 Mounting on a Wall Before mounting the remote controller press the ON OFF operation button at the mounting location to make sure that the air conditioner operates from that location The indoor unit should make a beeping sound to indicate that it has ...

Страница 17: ...Then SUHVV DQG KROG WKH 5HVHW EXWWRQ ZLWK D pointed object such as the tip of a pen After 5 VHFRQGV UHOHDVH WKH EXWWRQ ILUVW WKHQ release the HIGH POWER and 1HR TIMER but tons oP 1 Test Run appears blinking in the remote controller clock display area 4 Each time the 1HR TIMER button is pressed the display changes as shown below Press this but ton 2 times to change the display to oP 7 Address setti...

Страница 18: ...nstalled level and vertically The power and voltage are as specified Inter unit cables are securely inserted into the terminal block Inter unit cables are securely fixed The power cable and inter unit cables are not connected anywhere along their paths The ground wire is securely connected Thermal insulation has been applied to the tubing connections Drain connections are secure and water drains p...

Отзывы: