background image

9

A must be within the range of 1/2"(13mm) to 23/32"(18mm). (Fig. 6-11)

If not within this range, malfunction or other trouble may occur.

Ceiling opening
dimension

Ceiling side

A

Indoor unit

3-5.  Checking the Drainage

After wiring and drain piping are completed, use the following pro-
cedure to check that the water will drain smoothly. For this, pre-
pare a bucket and wiping cloth to catch and wipe up spilled water.

Be sure to do the wiring between the units before installing the
ceiling panel. (Refer to 3-8. Wiring Instructions for Inter-unit
Connections)

(1) Turn on the power. (Here, “power” refers to the power supply

from the outdoor unit.)

(2) Slowly pour approx. 16 ounces (500 ml) of water into the drain

pan to check drainage. (Fig. 6-10a)

(3) Remove the 2 screws from the control box cover, then open

the cover. Be careful not to drop the cover at this time.

(4) Disconnect the FS 3P connector (red) on the control PCB and

operate the drain pump. (Fig. 6-10b) Check the water flow
through the transparent drain pipe and see if there is any
leakage.

(5) When the check of drainage is complete, reconnect the FS

3P connector and remount the control cover.

3-6.  How to Install the Ceiling Panel

Checking the unit position

(1) Check that the ceiling hole is 23-5/8" (600 mm) 

23-5/8"

(600 mm) (Fig. 6-11)

(2) Confirm that the position of the indoor unit and the ceiling

as shown in the diagram. If the positions of the ceiling sur-
face and unit do not match, air leakage, water leakage, flap
operation failure, or other problems may occur. (Fig. 6-11)

The drain pump will continue to
operate for a minimum of 6 min-
utes after the FS 3P connector is
reconnected.

CAUTION

Never place the panel face-down. Neither hang it ver-
tically nor place it on top of a projecting object. Plac-
ing it face-down will damage the surface.

Do not touch the flap or apply force to it. (This may
cause flap malfunction.) (Fig. 6-12)

CAUTION

3-6-1.  Before Installing the Ceiling Panel

(1) Remove the air-intake grille and air filter from the ceiling

panel.

a) Press on and slide the two latches of the air-intake grille

with your thumb in the direction shown by the arrow 
to open the grille. (Figs. 6-13 and 6-14)

b) With the air-intake grille opened, remove the grille hinge

from the ceiling panel by sliding it in the direction shown
by the arrow 

. (Fig. 6-15)

2

1

Fig. 6-10a

Fig. 6-12

Fig. 6-13

Water drain

Control box

Drain pan outlet

Water

Plastic container
for water intake

Over 4"
(100mm)

(Approx. 16 ounces (500m  ) )

Flap

NO

/DWFK

Air-intake grille

Ceiling panel

Air-intake grille hinge

1

1

2

Fig. 6-11

Fig. 6-14

Fig. 6-15

FS

)/$3

Control box

RC

IND

Fig. 6-10b

Содержание CS-KS18NB4UW & CZ-18BT1U + CU-KS18NKU

Страница 1: ...A 3 INSTALLATION INSTRUCTIONS CS MKS9NB4U CZ 18BT1U CS MKS12NB4U CZ 18BT1U CS KS18NB4UW CZ 18BT1U APPENDIX C 852 6 4190 582 00 0 ...

Страница 2: ... THE INDOOR UNIT 7 3 1 Preparation for Suspending 3 2 Suspending the Indoor Unit 3 3 Placing the Unit Inside the Ceiling 3 4 Installing the Drain Piping 3 5 Checking the Drainage 3 6 How to Install the Ceiling Panel 3 7 Wiring Instructions 3 8 Wiring Instructions for Inter unit Connections 4 HOW TO TEST RUN THE AIR CONDITIONER 14 5 REMOTE CONTROLLER INSTALLATION POSITION 15 5 1 Mounting on a Wall ...

Страница 3: ...azard 7R SUHYHQW SRVVLEOH KD DUGV IURP LQVXODWLRQ IDLOXUH the unit must be grounded When Transporting Be careful when picking up and moving the indoor and out door units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin alu minum fins on the air conditioner can cut your fingers When Installing Select an installation location which is rigid and...

Страница 4: ... ILQJHUV DQG FORWKLQJ DZD IURP DQ PRYLQJ parts OHDQ XS WKH VLWH DIWHU RX ILQLVK UHPHPEHULQJ WR FKHFN that no metal scraps or bits of wiring have been left inside the unit being serviced Others 9HQWLODWH DQ HQFORVHG DUHDV ZKHQ LQVWDOOLQJ RU WHVWLQJ the refrigeration system Escaped refrigerant gas on contact with fire or heat can produce dangerously toxic gas RQILUP XSRQ FRPSOHWLQJ LQVWDOODWLRQ WKDW...

Страница 5: ...nits and make sure all accessory parts listed are with the system before beginning 1 1 Tools Required for Installation not supplied 1 Standard screwdriver 2 Phillips head screwdriver 3 Knife or wire stripper 4 Tape measure 5 Carpenter s level 6 Sabre saw or key hole saw 7 Hacksaw 8 Core bits 9 Hammer 10 Drill 11 Tube cutter 12 Tube flaring tool 13 Torque wrench 14 Adjustable wrench 15 Reamer for d...

Страница 6: ...ition from which every corner of the room can be uniformly cooled select a location that will hold the weight of the unit select a location where tubing and drain hose have the shortest run to the outside allow room for operation and maintenance as well as unrestricted air flow around the unit Fig 1 install the unit within the maximum elevation difference H1 H2 H3 H4 above or below the outdoor uni...

Страница 7: ...ds securely If a tube is left open for an extended time moisture in the air inside the tubing may condense into water droplets and lead to water contamination of the refrig erant circuit In order to prevent insulation breakdown and ground faults do not allow wiring ends to come in contact with rainwater or be subjected to condensation or dew Apply sufficient thermal insulation to the refrigerant t...

Страница 8: ...ram The dia gram shows the relationship between the positions of the suspension fitting unit and panel Fig 6 2 3 3 Placing the Unit Inside the Ceiling 1 Be sure to remove the fan protection 4pcs for transportation before hanging up the indoor unit 2 When placing the unit inside the ceiling determine the pitch of the suspension bolts using the supplied full scale installation diagram Fig 6 3 Tubing...

Страница 9: ...ll the drain hose first place 1 of the 2 hose bands over the unit drain port and the other hose band over the hard PVC pipe not supplied Then connect both ends of the supplied drain hose Fig 6 5 3 On the unit drain side grasp the hose band with pliers and insert the drain hose all the way to the base If other commercially available hose bands are used the drain hose may become pinched or wrinkled ...

Страница 10: ...nit position 1 Check that the ceiling hole is 23 5 8 600 mm 23 5 8 600 mm Fig 6 11 2 Confirm that the position of the indoor unit and the ceiling as shown in the diagram If the positions of the ceiling sur face and unit do not match air leakage water leakage flap operation failure or other problems may occur Fig 6 11 The drain pump will continue to operate for a minimum of 6 min utes after the FS ...

Страница 11: ... the unit and the ceiling panel or between the ceiling panel and the ceiling surface If there is a gap between the panel and the ceiling leave the ceiling panel attached and make fine adjustments to the installation height of the unit to eliminate the gap with the ceiling CAUTION Fig 6 17 Fig 6 18 Fig 6 19 Corner cover Indicator cover Press Pull up 2 1 latch Temporary latches Temporary DRAIN mark ...

Страница 12: ...ignal will not be received If the connectors are not connected the auto flap will not operate Be sure to connect them securely A Attaching the corner cover 1 Check that the safety strap from the corner cover is fas tened to the ceiling panel pin as shown in the figure Fig 6 23 2 Use the supplied screws to attach the corner cover to the ceiling panel B Attaching the air intake grille To install the...

Страница 13: ...used exclusively for each unit with a power supply disconnect and circuit breaker for overcurrent protection provided in the exclusive line 3 To prevent possible hazards due to insulation failure the unit must be grounded 4 Each wiring connection must be done tightly and in accordance with the wiring system diagram Wrong wiring may cause the unit to misoperate or become damaged 5 Do not allow wiri...

Страница 14: ... the terminal screw 4 Shape the loop wire properly place it on the termi nal plate and fix it securely with the removed termi nal screw using a screwdriver For stranded wiring 1 Cut the wire end with a cutting pliers then strip the insulation to expose the stranded wiring about 3 8 10 mm and tightly twist the wire ends Figs 30 and 31 2 Using a screwdriver remove the terminal screw s on the termina...

Страница 15: ...PLQXWHV WKH V VWHP VKLIWV LQWR FRROLQJ operation and cool air will start to be felt Cooling mode test run is unaffected by the room tempera ture 3 Press the ON OFF operation button of the remote controller again to stop the test run Fig 33 LQDOO SUHVV WKH 5HVHW EXWWRQ RI WKH UHPRWH controller to release it from Test Run mode to return to normal mode Fig 33 µ DQG R3 µ ZLOO GLVDSSHDU IURP WKH UHPRWH...

Страница 16: ...ere is an obstacle between the remote con troller and the air conditioner since a check signal is sent from the remote controller every 5 minutes 5 1 Mounting on a Wall Before mounting the remote controller press the ON OFF operation button at the mounting location to make sure that the air conditioner operates from that location The indoor unit should make a beeping sound to indicate that it has ...

Страница 17: ...Then SUHVV DQG KROG WKH 5HVHW EXWWRQ ZLWK D pointed object such as the tip of a pen After 5 VHFRQGV UHOHDVH WKH EXWWRQ ILUVW WKHQ release the HIGH POWER and 1HR TIMER but tons oP 1 Test Run appears blinking in the remote controller clock display area 4 Each time the 1HR TIMER button is pressed the display changes as shown below Press this but ton 2 times to change the display to oP 7 Address setti...

Страница 18: ...nstalled level and vertically The power and voltage are as specified Inter unit cables are securely inserted into the terminal block Inter unit cables are securely fixed The power cable and inter unit cables are not connected anywhere along their paths The ground wire is securely connected Thermal insulation has been applied to the tubing connections Drain connections are secure and water drains p...

Отзывы: