92
13.14.1.2 Information
Log
•
The signal from Infrared sensors will be log to human activity database for further analysis.
13.14.1.3 Human Position Analysis
•
According to Area of Living, frequency of activity, the system will analyze the human position away from the
indoor unit.
13.14.1.4 Human Activity Level Judgment
•
Human Activity Level is judged based on the frequency of pulses detected by the infrared sensors within a
timeframe. The activity level will be categorized into High, Normal, Low level.
•
When a pulse is detected within this timeframe, the status of human presence is judged.
•
When there is no signal detection continues for 40 minutes or more, the status of human absence is judged.
13.14.1.5 Determination of Presence or Absence
•
Human presence status shall be determined based on the human presence status of each area.
•
When all area has been detected absent for more than 40 minutes then it will judge as absence.
13.14.1.6 Area of Living Classification Judgment
•
The system is able to judge area of living according to human activity database, classified as following:
o
(Zone I) Living Area – In front of television, dining table, etc.
o
(Zone II) Walkway – Human detection is relatively less.
o
(Zone III) Non-Living Area – Near windows, wall, etc.
13.14.1.7 Target Area and Position Judgment
•
By default, the system will judge the indoor unit installation position according to human activities and will reset
the louver center position::
o
Non-Living Area at Position A – Indoor unit installed at left side of the room.
o
Non-Living Area at Position C – Indoor unit installed at right side of the room.
o
Other than above – Indoor unit installed at center of the room.
•
Every 4 hours, the Judgment will restart.
•
Target area is judged according to human position analysis result.
13.14.1.8 Setting Temperature and Fan Speed Shift
* During low activity, fan speed 1 tap up for first 15 minutes or until set temperature is reached.
** During human absence, maximum fan speed for COOL/DRY mode is medium fan.
Содержание CS-E7PKEW
Страница 28: ...28 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 29: ...29 5 Dimensions 5 1 Indoor Unit 5 1 1 CS E7PK CS E9PK CS E12PK CS E15PK CS XE7PK CS XE9PK CS XE12PK CS XE15PK ...
Страница 30: ...30 5 1 2 CS E18PK CS E21PK CS E24PK CS E28PK CS XE18PK CS XE21PK ...
Страница 31: ...31 5 2 Outdoor Unit 5 2 1 CU E7PKE CU E9PKE 5 2 2 CU E12PKE CU E15PKE ...
Страница 32: ...32 5 2 3 CU E18PKE CU E21PKE ...
Страница 33: ...33 5 2 4 CU E24PKE CU E28PKE ...
Страница 42: ...42 8 1 2 CS E28PKES ...
Страница 48: ...48 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 56: ...56 10 1 6 Human Activity Sensor Printed Circuit Board ...
Страница 57: ...57 10 2 Outdoor Unit 10 2 1 CU E7PKE ...
Страница 58: ...58 10 2 2 CU E9PKE CU E12PKE CU E15PKE ...
Страница 59: ...59 10 2 3 CU E18PKE CU E21PKE ...
Страница 60: ...60 10 2 4 CU E24PKE CU E28PKE ...
Страница 66: ...66 ...
Страница 68: ...68 For Gas side piping please refer table and diagram below ...
Страница 76: ...76 ...
Страница 140: ...140 Figure 3 Figure 4 18 1 1 3 To remove discharge grille Figure 5 ...
Страница 141: ...141 18 1 1 4 To remove control board Figure 6 18 1 1 5 To remove cross flow fan and indoor fan motor Figure 7 ...
Страница 142: ...142 Figure 8 Figure 9 ...
Страница 143: ...143 Figure 10 ...
Страница 145: ...145 18 2 1 3 To remove power electronic controller Figure 13 Figure 14 Figure 15 Figure 16 ...
Страница 147: ...147 Figure 20 Figure 21 ...
Страница 148: ...148 Figure 22 ...