background image

31 

8.2.2 CU-E18NKD 

 

 

Содержание CS-E7NKDW

Страница 1: ...ON OF LOW TEMPERATURE In order to avoid frostbite be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit This service information is designed for experienced...

Страница 2: ...o Restart Control 54 12 10 Indication Panel 54 12 11 nanoe G Operation 55 12 12 Mild Dry Cooling Operation 57 12 13 ECONAVI and AUTO COMFORT Operation 58 13 Operation Control For Multi Split Connectio...

Страница 3: ...y recommended to install with Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire in case equipment breakdown or insulation breakdown 10...

Страница 4: ...d aluminium fin It may cause injury 5 Select an installation location which is easy for maintenance 6 Pb free solder has a higher melting point than standard solder typically the melting point is 50 F...

Страница 5: ...ooling Outdoor Noise H L Power Level dB 60 60 61 61 kW 0 75 2 80 4 00 0 75 2 80 4 00 0 85 3 40 5 00 0 85 3 40 5 00 BTU h 2560 9550 13600 2560 9550 13600 2900 11600 17100 2900 11600 17100 Capacity Kcal...

Страница 6: ...3 400 Hi Heat m 3 min ft 3 min 11 4 400 11 9 420 Cool m 3 min ft 3 min 11 6 410 11 7 410 Indoor Airflow SHi Heat m 3 min ft 3 min 12 0 424 12 1 427 Cool m 3 min ft 3 min 32 4 1145 33 9 1195 29 4 1040...

Страница 7: ...ry Bulb Wet Bulb Maximum 32 23 32 23 Cooling Minimum 16 11 16 11 Maximum 30 30 Indoor Operation Range Heating Minimum 16 16 Maximum 43 26 43 26 Cooling Minimum 16 11 16 11 Maximum 24 18 24 18 Outdoor...

Страница 8: ...ng Outdoor Noise H L Power Level dB 63 63 64 64 kW 0 85 4 40 6 70 0 85 4 40 6 70 0 85 5 30 6 80 0 85 5 30 6 80 BTU h 2900 15000 22800 2900 15000 22800 2900 18100 23200 2900 18100 23200 Capacity Kcal h...

Страница 9: ...12 5 440 Hi Heat m 3 min ft 3 min 12 8 450 13 4 475 Cool m 3 min ft 3 min 13 1 463 13 3 470 Indoor Airflow SHi Heat m 3 min ft 3 min 13 3 470 13 6 480 Cool m 3 min ft 3 min 30 6 1080 31 0 1095 31 0 10...

Страница 10: ...lb Dry Bulb Wet Bulb Maximum 32 23 32 23 Cooling Minimum 16 11 16 11 Maximum 30 30 Indoor Operation Range Heating Minimum 16 16 Maximum 43 26 43 26 Cooling Minimum 16 11 16 11 Maximum 24 18 24 18 Outd...

Страница 11: ...dB A 47 47 Cooling Outdoor Noise H L Power Level dB 61 61 kW 0 98 5 80 8 00 0 98 5 80 8 00 BTU h 3340 19800 27300 3340 19800 27300 Capacity Kcal h 840 4990 6880 840 4990 6880 Running Current A 7 2 6 9...

Страница 12: ...e Heat m 3 min ft 3 min 16 0 565 Cool m 3 min ft 3 min 16 3 575 Hi Heat m 3 min ft 3 min 17 9 630 Cool m 3 min ft 3 min 18 1 639 Indoor Airflow SHi Heat m 3 min ft 3 min 18 5 653 Cool m 3 min ft 3 min...

Страница 13: ...ng Minimum 16 Maximum 43 26 Cooling Minimum 16 11 Maximum 24 18 Outdoor Operation Range Heating Minimum 5 6 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C...

Страница 14: ...14 Multi Split Combination Possibility o A single outdoor unit enables air conditioning of up to two separate rooms for U 2E15GBE U 2E18CBPG...

Страница 15: ...15 Outdoor Unit U 2E15GBE Outdoor Unit U 2E18CBPG...

Страница 16: ...16 Outdoor Unit U 3E18JBE...

Страница 17: ...17 Outdoor Unit U 4E23JBE...

Страница 18: ...18...

Страница 19: ...0 75 1 75HP and 20 meters 2 0 2 25HP during single split connection only Easy to use remote control Quality Improvement o Random auto restart after power failure for safety restart operation o Gas lea...

Страница 20: ...20 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...

Страница 21: ...21 5 Dimensions 5 1 Indoor Unit 5 1 1 CS E7NK CS E9NK CS E12NK CS E15NK...

Страница 22: ...22 5 1 2 CS E18NK...

Страница 23: ...23 5 2 Outdoor Unit 5 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD 5 2 2 CU E18NKD...

Страница 24: ...24 6 Refrigeration Cycle Diagram 6 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD...

Страница 25: ...25 6 2 CU E18NKD...

Страница 26: ...26 7 Block Diagram 7 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD...

Страница 27: ...27 7 2 CU E18NKD...

Страница 28: ...28 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 CS E7NKDW CS E9NKDW CS E12NKDW CS E15NKDW...

Страница 29: ...29 8 1 2 CS E18NKDW...

Страница 30: ...30 8 2 Outdoor Unit 8 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD...

Страница 31: ...31 8 2 2 CU E18NKD...

Страница 32: ...32 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 CS E7NKDW CS E9NKDW CS E12NKDW CS E15NKDW...

Страница 33: ...33 9 1 2 CS E18NKDW...

Страница 34: ...34 9 2 Outdoor Unit 9 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD...

Страница 35: ...35 9 2 2 CU E18NKD...

Страница 36: ...36 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...

Страница 37: ...37 10 1 2 Indicator and Receiver Printed Circuit Board 10 1 3 High Voltage Power Supply Printed Circuit Board 10 1 4 Comparator Printed Circuit Board...

Страница 38: ...38 10 1 5 Human Activity Sensor Printed Circuit Board...

Страница 39: ...39 10 2 Outdoor Unit 10 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD...

Страница 40: ...40 10 2 2 CU E18NKD...

Страница 41: ...the condenser is not obstructed There should not be any animal or plant which could be affected by hot air discharged Keep the spaces indicated by arrows from wall ceiling fence or other obstacles Do...

Страница 42: ...s o Always mount the installation plate horizontally by aligning the marking off line with the thread and using a level gauge 2 Drill the piping plate hole with 70 mm hole core drill o Line according...

Страница 43: ...43 11 2 3 1 For the right rear piping 11 2 3 2 For the right and right bottom piping 11 2 3 3 For the embedded piping This can be used for left rear piping and bottom piping also...

Страница 44: ...d 3 Bind all the indoor and outdoor connection cable with tape and route the connection cable via the escapement 4 Remove the tapes and connect the connection cable between indoor unit and outdoor uni...

Страница 45: ...ipe cutter and then remove the burrs 2 Remove the burrs by using reamer If burrs are not removed gas leakage may be caused Turn the piping end down to avoid the metal powder entering the pipe 3 Please...

Страница 46: ...with fingers Further tighten the flare nut with torque wrench in specified torque as stated in the table Connecting the Piping to Outdoor Decide piping length and then cut by using pipe cutter Remove...

Страница 47: ...OPEN using a hexagonal wrench 4 mm 8 Mount valve caps onto the 2 way valve and the 3 way valve o Be sure to check for gas leakage If gauge needle does not move from 0 cmHg 0 MPa to 76 cmHg 0 1 MPa in...

Страница 48: ...Disconnecting means should have minimum 3 0 mm contact gap Earth wire shall be Yellow Green Y G in colour and longer than other AC wires for safety reason 11 3 5 Piping Insulation 1 Please carry out...

Страница 49: ...settings and the operation environment The final shifted value will be used as internal setting temperature and it is updated continuously whenever the electrical power is supplied to the unit 12 1 2...

Страница 50: ...perature the value of T1 will increase up to 10 C T2 will decrease by 3 C and T3 will decrease up to 8 C The Auto Operation Mode shifting will take place whenever operation mode changed from Cooling S...

Страница 51: ...by vertical vanes Control of airflow direction can be automatic angles of direction is determined by operation mode heat exchanger temperature and intake air temperature and manual angles of direction...

Страница 52: ...ode operation the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below It does not swing during fan motor stop Operation Mode Vane Angle A 70 110 Heating with heat exch...

Страница 53: ...satisfied quiet operation stops a POWERFUL QUIET button is pressed again b Stop by OFF ON switch c Timer off activates d AUTO COMFORT button is pressed e ECONAVI button is pressed f Mild Dry Cooling b...

Страница 54: ...off during the operation of air conditioner the compressor will re operate within three to four minutes there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected rand...

Страница 55: ...pressed no signal is sent to the unit and no change on remote control display Auto Fan Speed for nanoe G operation changes from SHi to Hi after 4 hours of operation Airflow direction control o During...

Страница 56: ...supplies power to the nanoe G system When abnormal discharge occurs for 24 times continuously nanoe G indicator blinks o Troubleshooting method Press nanoe G button or OFF ON button to stop the operat...

Страница 57: ...ing indicators turns ON at remote control display Mild dry cooling operation is unavailable when the unit is operating Auto mode Soft Dry mode Patrol individual operation or e ion individual operation...

Страница 58: ...Sensor power ON and end after 30 seconds b Control content Judge ECONAVI and AUTO COMFORT Sensor power level every 100ms c Abnormal Judgment condition When ECONAVI and AUTO COMFORT Sensor has continue...

Страница 59: ...t During ECONAVI and AUTO COMFORT operation the internal setting temperature and fan speed are adjusted in order to provide comfort and energy saving ECONAVI Start condition Press ECONAVI button ECONA...

Страница 60: ...e OFF ECONAVI and AUTO COMFORT operation will not be ON automatically When unit is turn on by ON Timer and ECONAVI and AUTO COMFORT operation is OFF during previous operation before OFF ECONAVI and AU...

Страница 61: ...ing ECONAVI AUTO COMFORT mode ON when check signal is received if 1 or 2 is detected ECONAVI AUTO COMFORT LED start blinking ECONAVI AUTO COMFORT sensor operation stops but the unit operates as normal...

Страница 62: ...tting temperature Capability supply OFF point 13 3 Heating Operation 13 3 1 Thermostat control Capability supply to indoor unit is OFF Expansion valve closed when Intake Air Temperature Internal setti...

Страница 63: ...remote control setting temperature the powerful operation continue until user cancel the Powerful operation by pressing powerful button again 13 7 Auto restart control When the power supply is cut of...

Страница 64: ...6 93 15 06 7 59 15 06 11 81 14 75 Cooling Soft Dry B 3 33 15 06 4 20 15 06 6 42 15 06 7 23 15 06 8 9 14 75 Heating 4 46 15 06 5 57 15 06 8 10 15 06 8 62 15 06 10 07 14 75 The first 30 minutes of cooli...

Страница 65: ...r suction temperature indoor piping temperature is below 4 C o During Heating operations Indoor piping temperature indoor suction is under 5 C Control contents o Compressor stops and restart after 3 m...

Страница 66: ...or heat exchanger is higher than 5 C At the same time indoor fan speed will be higher than during its normal operation If indoor heat exchanger temperature is higher than 5 C for 5 minutes the fan spe...

Страница 67: ...r Air Temperature Control The Max current value is regulated when the outdoor air temperature rise above 16 C E7 15NK and 14 C E18NK in order to avoid compressor overloading 14 3 3 Overload Protection...

Страница 68: ...on 3 REMOTE CONTROL NUMBER SWITCH MODE The Remote Control Number Switch Mode will be activated if the Auto OFF ON button is pressed continuously for more than 11 seconds 3 beep sounds will occur at 11...

Страница 69: ...mote Control Receiving Sound OFF ON Mode is restarted 15 2 Remote Control Button 15 2 1 SET BUTTON To check remote control transmission code and store the transmission code to EEPROM o Press SET butto...

Страница 70: ...d a fan The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions the standard values for them are shown in the table on the right Normal Pressure and Out...

Страница 71: ...Electric current during operation Low Pressure High Pressure Electric current during operation Insufficient refrigerant gas leakage Clogged capillary tube or Strainer Short circuit in the indoor unit...

Страница 72: ...Display Memorized Error Protective Operation status 1 Turn power on 2 Press the CHECK button on the remote controller continuously for 5 seconds 3 will be displayed on the remote controller display No...

Страница 73: ...73 16 3 Error Code Table...

Страница 74: ...74...

Страница 75: ...ransmission is checked whether it is normal Malfunction Caused Faulty indoor unit PCB Faulty outdoor unit PCB Indoor unit outdoor unit signal transmission error due to wrong wiring Indoor unit outdoor...

Страница 76: ...re interconnected Malfunction Caused Wrong models interconnected Wrong indoor unit or outdoor unit PCBs mounted Indoor unit or outdoor unit PCBs defective Indoor outdoor unit signal transmission error...

Страница 77: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors Malfunction Cause...

Страница 78: ...Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors Malfunction Caused F...

Страница 79: ...ons A current transformer CT is detected by checking the compressor running frequency rated frequency and CT detected input current less than 0 65A for continuously 20 seconds Malfunction Caused CT de...

Страница 80: ...termine abnormal fan motor feedback of rotation 2550rpm or 50rpm Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the...

Страница 81: ...Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors Malfunction Caused...

Страница 82: ...Abnormal Malfunction Decision Conditions During standby of cooling and heating operation e ion breakdown occurs and air conditioner stops operation Malfunction Caused Faulty indoor main PCB Faulty in...

Страница 83: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors Malfunction Caused Faul...

Страница 84: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors Malfunction Caused Fau...

Страница 85: ...ion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors Malfunction C...

Страница 86: ...ction Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor heat exchanger temperature sensor are used to determine sensor errors Malfunction...

Страница 87: ...lfunction Decision Conditions The supply power is detected for its requirement by the indoor outdoor transmission Malfunction Caused Wrong models interconnected Wrong indoor unit and outdoor unit PCBs...

Страница 88: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor heat sink temperature sensor are used to determine sensor errors Malfunction Cause...

Страница 89: ...ecision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor errors Malfunction Caused Fault...

Страница 90: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor liquid pipe temperature sensor are used to determine sensor errors Malfunction Cau...

Страница 91: ...ration is used to determine abnormal fan motor Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the fan motor Operati...

Страница 92: ...ture detected by the indoor pipe temperature sensor is above 60 C Malfunction Caused Air short circuit at indoor unit Clogged indoor unit air filter Dust accumulation on the indoor unit heat exchanger...

Страница 93: ...takes place when indoor pipe temperature is lower than 2 C Malfunction Caused Air short circuit at indoor unit Clogged indoor unit air filter Dust accumulation on the indoor unit heat exchanger 2 3 w...

Страница 94: ...nditions When heating operation when indoor pipe temperature is below 10 C When cooling operation when indoor pipe temperature is above 45 C Malfunction Caused Connector in poor contact Faulty sensor...

Страница 95: ...ature and indoor pipe temperature is above 10 C or indoor pipe temperature is below 1 0 C Remark When the indoor standby unit is freezing the outdoor unit transfers F17 error code to the corresponding...

Страница 96: ...eration of cooling and heating when Power Factor Correction PFC protection circuitry at the outdoor unit main PCB senses abnormal high DC voltage level Malfunction Caused DC voltage peak due to power...

Страница 97: ...ing the CT detected input current value and the compressor running frequency During startup and operating of cooling and heating input current 8 78 256 A Hz x compressor running frequency 0 25 Gas sho...

Страница 98: ...on Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit Malfunction Caused Compressor terminal disconnect F...

Страница 99: ...re data 61 C is detected by the outdoor pipe temperature sensor Malfunction Caused Air short circuit at indoor unit Dust accumulation on the indoor unit heat exchanger 2 3 way valve closed Faulty outd...

Страница 100: ...ed o Heat Sink Overheating During operation of cooling and heating when heat sink temperature data 90 C is detected by the heat sink temperature sensor Malfunction Caused IPM overheats due to short ci...

Страница 101: ...ing and heating when compressor tank temperature data 112 C is detected by the compressor tank temperature sensor Malfunction Caused Faulty compressor tank temperature sensor 2 3 way valve closed Refr...

Страница 102: ...on of cooling and heating when an input over current X value in Total Running Current Control is detected by checking the input current value being detected by current transformer CT with the compress...

Страница 103: ...ubleshooting Checking the power transistor Never touch any live parts for at least 10 minutes after turning off the circuit breaker If unavoidable necessary to touch a live part make sure the power tr...

Страница 104: ...itor has discharged sufficiently before proceeding with repair work Failure to heed this caution may result in electric shocks 17 1 CS E7NK CS E9NK CS E12NK CS E15NK 17 1 1 Indoor Electronic Controlle...

Страница 105: ...105 Figure 3 Figure 4 17 1 1 3 To remove discharge grille Figure 5...

Страница 106: ...106 17 1 1 4 To remove control board Figure 6 17 1 1 5 To remove cross flow fan and indoor fan motor Figure 7 Figure 8...

Страница 107: ...107 Figure 9 Figure 10...

Страница 108: ...Indoor Electronic Controllers Cross Flow Fan and Indoor Fan Motor Removal Procedures 17 2 1 1 To remove front grille Figure 11 17 2 1 2 To remove horizontal vane Figure 12 17 2 1 3 To remove electron...

Страница 109: ...109 Figure 14 Figure 15 17 2 1 4 To remove discharge grille Figure 16...

Страница 110: ...110 17 2 1 5 To remove control board Figure 17 17 2 1 6 To remove cross flow fan and indoor fan motor Figure 18 Figure 19...

Страница 111: ...111 Figure 20 Figure 21...

Страница 112: ...ing electronic controller be careful of electrostatic discharge 1 Remove the 3 screws of the Top Panel Fig 1 2 Remove the 6 screws of the Front Panel Fig 2 3 Remove the screw of the Terminal Board Cov...

Страница 113: ...ve the 10 screws of the Front Panel Fig 2 3 Remove the Top Cover of the Electronic Controller Fig 3 4 Remove the Control Board Fig 4 5 Remove the 8 screws of the Electronic Controller Fig 5 Caution Wh...

Страница 114: ...39 41 43 Outdoor Air Temperature C Outlet Air Temperature C 220 230 1 700 1 900 2 100 2 300 2 500 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 Outdoor Air Temperature C Cooling Capacity kW...

Страница 115: ...iping Length m Cooling Capacity kW 1 070 1 080 1 090 1 100 1 110 1 120 1 130 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Gas Side Piping Pressure MPa 18 400 18 500 18 600 18 700 18 800 18 900 19 0...

Страница 116: ...emperature C Outlet Air Temperature C 220 230 1 800 2 000 2 200 2 400 2 600 2 800 3 000 3 200 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 Outdoor Air Temperature C Heating Capacity kW 2 500 2 700 2 900 3 100 3 3...

Страница 117: ...0 11 12 13 14 15 Piping Length m Heating Capacity kW 2 600 2 620 2 640 2 660 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Gas Side Piping Pressure MPa 31 900 32 000 32 100 32 200 32 300 32 400 3 4...

Страница 118: ...t Air Temperature C 220 230 2 100 2 300 2 500 2 700 2 900 3 100 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 Outdoor Air Temperature C Cooling Capacity kW 1 300 1 800 2 300 2 800 3 300 5 7...

Страница 119: ...14 15 Piping Length m Cooling Capacity kW 1 070 1 080 1 090 1 100 1 110 1 120 1 130 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Gas Side Piping Pressure MPa 17 100 17 200 17 300 17 400 17 500 17 6...

Страница 120: ...erature C Outlet Air Temperature C 220 230 2 200 2 400 2 600 2 800 3 000 3 200 3 400 3 600 3 800 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 Outdoor Air Temperature C Heating Capacity kW 2 900 3 100 3 300 3 500...

Страница 121: ...9 10 11 12 13 14 15 Piping Length m Heating Capacity kW 2 340 2 360 2 380 2 400 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Gas Side Piping Pressure MPa 34 400 34 500 34 600 34 700 34 800 34 900 3...

Страница 122: ...utlet Air Temperature C 220 230 3 000 3 200 3 400 3 600 3 800 4 000 4 200 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 Outdoor Air Temperature C Cooling Capacity kW 2 100 2 600 3 100 3 600...

Страница 123: ...14 15 Piping Length m Cooling Capacity kW 0 920 0 930 0 940 0 950 0 960 0 970 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Gas Side Piping Pressure MPa 14 900 15 000 15 100 15 200 15 300 15 400 15...

Страница 124: ...emperature C Outlet Air Temperature C 220 230 2 800 3 300 3 800 4 300 4 800 5 300 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 Outdoor Air Temperature C Heating Capacity kW 4 300 4 500 4 700 4 900 5 100 5 300 5 5...

Страница 125: ...2 13 14 15 Piping Length m Heating Capacity kW 2 420 2 440 2 460 2 480 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Gas Side Piping Pressure MPa 35 100 35 200 35 300 35 400 35 500 35 600 3 4 5 6 7...

Страница 126: ...C Outlet Air Temperature C 220 230 3 600 3 800 4 000 4 200 4 400 4 600 4 800 5 000 5 200 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 Outdoor Air Temperature C Cooling Capacity kW 2 900 3...

Страница 127: ...13 14 15 Piping Length m Cooling Capacity kW 0 890 0 900 0 910 0 920 0 930 0 940 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Gas Side Piping Pressure MPa 14 900 15 000 15 100 15 200 15 300 15 400...

Страница 128: ...emperature C Outlet Air Temperature C 220 230 3 400 3 900 4 400 4 900 5 400 5 900 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 Outdoor Air Temperature C Heating Capacity kW 5 600 5 800 6 000 6 200 6 400 6 600 6 8...

Страница 129: ...3 14 15 Piping Length m Heating Capacity kW 2 740 2 760 2 780 2 800 2 820 3 4 5 6 7 8 9 10 11 12 13 14 15 Piping Length m Gas Side Piping Pressure MPa 38 400 38 500 38 600 38 700 38 800 38 900 39 000...

Страница 130: ...Air Temperature C Outlet Air Temperature C 220 230 4 200 4 700 5 200 5 700 6 200 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 Outdoor Air Temperature C Cooling Capacity kW 3 100 4 100 5 10...

Страница 131: ...20 Piping Length m Cooling Capacity kW 0 900 0 910 0 920 0 930 0 940 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Piping Length m Gas Side Piping Pressure MPa 15 200 15 300 15 400 15 500 3 4 5 6 7...

Страница 132: ...erature C Outlet Air Temperature C 220 230 4 100 4 600 5 100 5 600 6 100 6 600 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 Outdoor Air Temperature C Heating Capacity kW 5 700 5 900 6 100 6 300 6 500 6 700 6 900...

Страница 133: ...17 18 19 20 Piping Length m Heating Capacity kW 2 770 2 780 2 790 2 800 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Piping Length m Gas Side Piping Pressure MPa 36 600 36 700 36 800 36 900 3 4 5 6...

Страница 134: ...50 2 55 1 89 0 54 2 37 1 82 0 58 2 15 1 73 0 63 22 0 C 2 97 2 04 0 51 2 77 1 96 0 55 2 58 1 89 0 59 2 35 1 81 0 64 CU E12NKD Outdoor Temp C 220 230V 30 35 40 46 Indoor wet bulb temp TC SHC IP TC SHC...

Страница 135: ...96 3 76 1 35 4 64 3 61 1 45 4 31 3 47 1 55 3 92 3 29 1 67 19 0 C 5 00 1 47 19 5 C 5 45 3 94 1 37 5 09 3 78 1 48 4 74 3 64 1 58 4 31 3 47 1 70 22 0 C 5 94 4 08 1 40 5 55 3 93 1 50 5 16 3 79 1 61 4 69 3...

Страница 136: ...cement Parts List 19 1 Indoor Unit 19 1 1 CS E7NKDW CS E9NKDW CS E12NKDW CS E15NKDW Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not...

Страница 137: ...NIC CONTROLLER COMPARATOR 1 CWA746769 O 21 LEAD WIRE PCB ECO 1 CWA67C9786 22 CONTROL BOARD CASING FOR PCB ECO 1 CWD933427 23 CONTROL BOARD TOP COVER 1 CWH131467 24 INDICATOR HOLDER 1 CWD933406 25 CONT...

Страница 138: ...K ABSORBER L 1 CWG713386 52 SHOCK ABSORBER R 1 CWG713387 53 C C CASE 1 CWG567358 CWG567359 CWG567360 CWG567361 NOTE All parts are supplied from PHAAM Malaysia Vendor Code 00029488 O marked parts are r...

Страница 139: ...139 19 1 2 CS E18NKDW Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 140: ...7C9935 22 CONTROL BOARD CASING FOR PCB ECO 1 CWD933455 23 CONTROL BOARD TOP COVER 1 CWH131467 24 INDICATOR HOLDER 1 CWD933406 25 CONTROL BOARD FRONT COVER CO 1 CWH13C1247 26 DISCHARGE GRILLE COMPLETE...

Страница 141: ...WF615103 50 BAG 1 CWG861498 51 SHOCK ABSORBER L 1 CWG713402 52 SHOCK ABSORBER R 1 CWG713403 53 C C CASE 1 CWG567974 NOTE All parts are supplied from PHAAM Malaysia Vendor Code 00029488 O marked parts...

Страница 142: ...2 Outdoor Unit 19 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service...

Страница 143: ...NAL COVER 1 CWH7080300J 22 SOUND PROOF BOARD 1 CWH151172 23A SOUND PROOF MATERIAL 1 CWG302443 CWG302293 24 SENSOR CO OUTDOOR COMPRESSOR TEMP 1 CWA50C2205 O 25 CONTROL BOARD COVER TOP 1 CWH131264 26 EL...

Страница 144: ...144 19 2 2 CU E18NKD Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 145: ...COMPLETE FOR EXP VALVE 1 CWA43C2257 29 SENSOR CO COMP DISCHARGE 2 CWA50C2656 O 30 SENSOR COMPLETE 1 CWA50C2517 O 31 REACTOR 1 G0C203J00003 33 TERMINAL BOARD ASSY 1 CWA28K1110J O 38 ELECTRONIC CONTROL...

Отзывы: