65
14.1.4 Compressor
Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
If compressor discharge temperature exceeds 107°C, compressor will be stopped, occurs 4 times per 20 minutes,
timer LED will be blinking. (“F97” is indicated.)
14.1.5 Low Pressure Prevention Control (Gas Leakage Detection)
Control start conditions
o
For 5 minutes, the compressor continuously operates and outdoor total current is between 0.75A and 0.95A
(E7/9/12/15NK), 1.38A and 1.65A (E18NK).
o
During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4°C.
o
During Heating operations :
Indoor piping temperature - indoor suction is under 5°C.
Control
contents
o
Compressor stops (and restart after 3 minutes).
o
If the conditions above happen 2 times within 20 minutes, the unit will:
Stop
operation
Timer LED blinks and “F91” indicated.
14.1.6 Low
Frequency
Protection Control 1
When the compressor operate at frequency lower than 24 Hz continued for 20 minutes, the operation frequency
will be changed to 23 Hz for 2 minutes.
14.1.7 Low
Frequency
Protection Control 2
When all the below conditions comply, the compressor frequency will change to lower frequency.
Temperature, T, for:
Cooling/Soft Dry
Heating
Indoor intake air (°C)
T < 14 or T
≥
30
T < 14 or T
≥
28
Outdoor air (°C)
T < 13 or T
≥
38
T < 4 or T
≥
24
Indoor heat exchanger (°C)
T < 30
T
≥
0
Содержание CS-E7NKDW
Страница 15: ...15 Outdoor Unit U 2E15GBE Outdoor Unit U 2E18CBPG...
Страница 16: ...16 Outdoor Unit U 3E18JBE...
Страница 17: ...17 Outdoor Unit U 4E23JBE...
Страница 18: ...18...
Страница 20: ...20 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control...
Страница 21: ...21 5 Dimensions 5 1 Indoor Unit 5 1 1 CS E7NK CS E9NK CS E12NK CS E15NK...
Страница 22: ...22 5 1 2 CS E18NK...
Страница 23: ...23 5 2 Outdoor Unit 5 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD 5 2 2 CU E18NKD...
Страница 24: ...24 6 Refrigeration Cycle Diagram 6 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD...
Страница 25: ...25 6 2 CU E18NKD...
Страница 26: ...26 7 Block Diagram 7 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD...
Страница 27: ...27 7 2 CU E18NKD...
Страница 28: ...28 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 CS E7NKDW CS E9NKDW CS E12NKDW CS E15NKDW...
Страница 29: ...29 8 1 2 CS E18NKDW...
Страница 30: ...30 8 2 Outdoor Unit 8 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD...
Страница 31: ...31 8 2 2 CU E18NKD...
Страница 32: ...32 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 CS E7NKDW CS E9NKDW CS E12NKDW CS E15NKDW...
Страница 33: ...33 9 1 2 CS E18NKDW...
Страница 34: ...34 9 2 Outdoor Unit 9 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD...
Страница 35: ...35 9 2 2 CU E18NKD...
Страница 36: ...36 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board...
Страница 38: ...38 10 1 5 Human Activity Sensor Printed Circuit Board...
Страница 39: ...39 10 2 Outdoor Unit 10 2 1 CU E7NKD CU E9NKD CU E12NKD CU E15NKD...
Страница 40: ...40 10 2 2 CU E18NKD...
Страница 73: ...73 16 3 Error Code Table...
Страница 74: ...74...
Страница 105: ...105 Figure 3 Figure 4 17 1 1 3 To remove discharge grille Figure 5...
Страница 106: ...106 17 1 1 4 To remove control board Figure 6 17 1 1 5 To remove cross flow fan and indoor fan motor Figure 7 Figure 8...
Страница 107: ...107 Figure 9 Figure 10...
Страница 109: ...109 Figure 14 Figure 15 17 2 1 4 To remove discharge grille Figure 16...
Страница 111: ...111 Figure 20 Figure 21...