31
11.3.3. Evacuation of the Equipment
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.
1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way valve.
• Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at a torque of 18 N
m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.
11.3.4. Connect the Cable to the Outdoor Unit
1. Remove the control board cover from the unit by
loosening the screw.
2. Cable connection to the power supply through Isolating
Devices (Disconnecting means).
• Connect approved type polychloroprene sheathed
power supply cord
3 x 1.5 mm
2
(3/4 ~ 1.75HP), 3 x 2.5
mm
2
(2.0 ~ 2.5HP) or 3 x 4.0 mm
2
(3.0HP) type
designation 245 IEC 57 or heavier cord to the terminal
board, and connect the others end of the cord to Isolating
Devices (Disconnecting means).
3.
Connection cable
between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 4 x 1.5 mm
2
flexible cord, type designation 245 IEC 57 or heavier
cord.
4. Connect the power supply cord and connecting cable
between indoor unit and outdoor unit according to the
diagram below.
• If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step above take the following measure:
- If the leak stops when the piping connections are tightened further, continue working from step .
- If the leak does not stop when the connections are retightened, repair the location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Take care of the liquid refrigerant, it may cause frostbite.
Содержание CS-E24MKES
Страница 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control ...
Страница 11: ...11 5 2 Outdoor Unit ...
Страница 12: ...12 6 Refrigeration Cycle Diagram ...
Страница 13: ...13 7 Block Diagram ...
Страница 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 15: ...15 8 2 Outdoor Unit 8 2 1 CU E24MKE ...
Страница 16: ...16 8 2 2 CU E28MKE ...
Страница 17: ...17 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 18: ...18 9 2 Outdoor Unit 9 2 1 CU E24MKE ...
Страница 19: ...19 9 2 2 CU E28MKE ...
Страница 20: ...20 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 22: ...22 10 1 6 Comparator Printed Circuit Board 10 1 7 Human Activity Sensor Printed Circuit Board ...
Страница 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 24: ...24 10 2 2 Power Printed Circuit Board ...
Страница 92: ...92 16 1 3 To remove power electronic controller ...
Страница 93: ...93 16 1 4 To remove discharge grille 16 1 5 To remove control board ...
Страница 94: ...94 16 1 6 To remove cross flow fan and indoor fan motor ...
Страница 95: ...95 ...
Страница 109: ...109 18 2 Outdoor Unit 18 2 1 CU E24MKE ...