86
15.5.26. F95 (Cooling High Pressure Abnormality)
Malfunction Decision Conditions
During operation of cooling, when outdoor unit heat exchanger high temperature data (61
C) is detected by the outdoor pipe
temperature sensor.
Malfunction Caused
• Air short circuit at indoor unit
• Dust accumulation on the indoor unit heat exchanger
• 2/3 way valve closed
• Faulty outdoor unit fan motor
• Excessive refrigerant
• Clogged expansion valve or strainer
• Faulty outdoor pipe temperature sensor
• Faulty outdoor unit PCB
Troubleshooting
Содержание CS-E24MKES
Страница 9: ...9 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control ...
Страница 11: ...11 5 2 Outdoor Unit ...
Страница 12: ...12 6 Refrigeration Cycle Diagram ...
Страница 13: ...13 7 Block Diagram ...
Страница 14: ...14 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 15: ...15 8 2 Outdoor Unit 8 2 1 CU E24MKE ...
Страница 16: ...16 8 2 2 CU E28MKE ...
Страница 17: ...17 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 18: ...18 9 2 Outdoor Unit 9 2 1 CU E24MKE ...
Страница 19: ...19 9 2 2 CU E28MKE ...
Страница 20: ...20 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 22: ...22 10 1 6 Comparator Printed Circuit Board 10 1 7 Human Activity Sensor Printed Circuit Board ...
Страница 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 24: ...24 10 2 2 Power Printed Circuit Board ...
Страница 92: ...92 16 1 3 To remove power electronic controller ...
Страница 93: ...93 16 1 4 To remove discharge grille 16 1 5 To remove control board ...
Страница 94: ...94 16 1 6 To remove cross flow fan and indoor fan motor ...
Страница 95: ...95 ...
Страница 109: ...109 18 2 Outdoor Unit 18 2 1 CU E24MKE ...