Table on Shifting Frequency Zone
Temperature, X (°C)
Zone
Frequency No. Shifting:
(Intake Air - Internal Setting)
Cooling Mode / Soft Dry Mode
Heating Mode
X
-2.5
0
Shift to Freq. MIN
Shift to Freq. MAX
-2.5
X
-1.5
1
Shift to Freq. MIN
Shift to Freq. MAX
-1.5
X
-1.0
2
-2 Freq. No.
+2 Freq. No.
-1.0
X
-0.5
3
-1 Freq. No.
+1 Freq. No.
-0.5
X
+1.0
4
Same Freq. No.
Same Freq. No.
+0.5
X
+1.0
5
+1 Freq. No.
-1 Freq. No.
+1.0
X
+1.5
6
+2 Freq. No.
-2 Freq. No.
+1.5
X
+2.5
7
Shift to Freq. MAX
Shift to Freq. MIN
X
+2.5
8
Shift to Freq. MAX
Shift to Freq. MIN
Besides, the range of operation frequency will change according to the setting environment as listed below:
Condition:
Freq. no. for E9CKP
Freq. no. for E12CKP/E15CKP
Remarks
MIN
MAX
MIN
MAX
Cooling Mode
1
15
1
16
(a)
- if remote controller set
28°C & fan speed =
Hi
7
15
7
16
(a), (c)
- if remote controller set
28°C & fan speed =
Me-, Me, Me+, Auto
5
15
6
16
(a), (c)
- if remote controller set
28°C & fan speed =
Lo
4
15
5
16
(a), (c)
- if Powerful Mode ON
7
15
7
16
(a), (c)
Soft Dry Mode
4
7
4
8
Heating Mode
1
30
1
30
(b)
- if remote controller set
18°C & fan speed =
Hi
10
30
10
30
(b), (d)
- if remote control set
18°C & fan speed =
Me-, Me, Me+, Auto
9
30
9
30
(b), (d)
- if remote controller set
18°C & fan speed =
Lo
8
30
8
30
(b), (d)
- if Powerful Mode ON
10
30
10
30
(b), (d)
Remark:
(a)
If frequency decreases from MAX, the following frequency performed will be depending to outdoor temperature, as given in below table
(for 30 seconds only) and then continues as normal rule.
Outdoor Temperature, X (°C)
Frequency No.
X
30
13
X
30
7
(b)
(If frequency increases from Freq. No. 17, the following frequency performed is as below (for 30 seconds only) and then continue as
normal rule.
Outdoor Temperature, X (°C)
Frequency No.
X
10
10
X
X
10
13
X
4
17
(c)
When temperature different (intake - setting) < -1.0 °C or Thermo-Off activated and only valid for 120 seconds; not applicable during Soft
Dry Mode, and Anti-freezing control.
(d)
When temperature different (intake - setting) > +1.5 °C or Thermo-Off activated and only valid for 130 seconds.
16
CS-E15CKP CU-E15CKP5
Содержание CS-E15CKP
Страница 8: ...4 Dimensions 8 CS E15CKP CU E15CKP5 ...
Страница 9: ...9 CS E15CKP CU E15CKP5 ...
Страница 10: ...5 Refrigeration Cycle Diagram 10 CS E15CKP CU E15CKP5 ...
Страница 11: ...6 Block Diagram 11 CS E15CKP CU E15CKP5 ...
Страница 12: ...7 Wiring Diagram 12 CS E15CKP CU E15CKP5 ...
Страница 39: ...IONIZE 42 43 44 41 39 CS E15CKP CU E15CKP5 ...
Страница 40: ...IONIZER IONIZER IONIZER IONIZER 40 CS E15CKP CU E15CKP5 ...
Страница 41: ...CZ SFD72P 41 CS E15CKP CU E15CKP5 ...
Страница 42: ...42 CS E15CKP CU E15CKP5 ...
Страница 43: ... H23 H27 H28 43 CS E15CKP CU E15CKP5 ...
Страница 44: ...44 CS E15CKP CU E15CKP5 ...
Страница 45: ...45 CS E15CKP CU E15CKP5 ...
Страница 75: ...13 Technical Data 75 CS E15CKP CU E15CKP5 ...
Страница 87: ...87 CS E15CKP CU E15CKP5 ...
Страница 88: ...How to use electronic circuit diagram 88 CS E15CKP CU E15CKP5 ...
Страница 89: ...18 1 REMOTE CONTROL 89 CS E15CKP CU E15CKP5 ...
Страница 90: ...18 2 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD 90 CS E15CKP CU E15CKP5 ...
Страница 91: ...18 3 PRINT PATTERN OUTDOOR UNIT PRINTED CIRCUIT BOARD VIEW 91 CS E15CKP CU E15CKP5 ...
Страница 92: ...92 CS E15CKP CU E15CKP5 ...
Страница 93: ...93 CS E15CKP CU E15CKP5 MAICO Printed in Malaysia ...
Страница 94: ......