8.1.2. Frequency Instruction for Compressor Operation
Operation of compressor is based on instructed frequency, continuously from indoor unit´s microcomputer after performing
temperature sampling and judgment.
There are total 30 different frequency values, which listed as Table on Frequency Number, to be instructed based on the
temperature judgment
Table on Frequency Number
No.
Frequency (Hz)
Remarks
E9CKP
E12CKP/E15CKP
1
12.0
12.0
Freq. MIN
2
15.0
15.0
3
18.0
18.0
4
21.0
21.0
5
23.0
23.0
6
25.0
25.0
7
26.0
28.0
8
30.0
32.0
9
33.0
36.0
10
35.0
40.0
11
36.0
44.0
12
38.0
48.0
13
39.0
52.0
Fc
14
40.0
57.0
15
47.0
62.0
Fc max. (E9CKP)
16
49.0
67.0
Fc max. (E12CKP/E15CKP)
17
56.0
68.5
Fh
18
58.0
72.0
19
63.0
76.0
20
66.0
80.0
21
70.0
85.0
22
73.0
88.0
23
77.0
91.0
24
80.0
94.0
25
83.0
98.0
26
86.0
102.0
27
87.0
104.0
28
88.0
106.0
29
89.0
108.0
30
90.0
110.0
Fh max.
For normal start of operation, including Thermo-OFF, Deice-Resuming, and remote controller ON-OFF starts, the compressor
starts to operate at frequency no. 8, values of 30Hz and 32Hz for E9CKP and E12CKP/E15CKP respectively, for 60 seconds.
The frequency to be judged and instructed, however, starts to judge once the air conditioner operated and the judgment will
continue every 30 seconds until it is stopped by all kinds of compressor off conditions. This judgment is based on the internal
temperature sampling that involving internal setting temperature and intake air temperature.
From the internal sampling, the temperature different (intake air temperature - internal setting temperature) will be used to judge
the Zone on which the frequency to be instructed for the initial operation of compressor (refer to Table on Initial Frequency Zone).
Table on Initial Frequency Zone
Temperature, X (°C)
Zone
Freq. No. - E9CKP
Freq. No. - E12CKP/E15CKP
(Intake Air - Internal Setting)
Cooling
Soft Dry
Heating
Cooling
Soft Dry
Heating
X
-2.5
0
1
4
30
1
4
30
-2.5
X
-1.5
1
1
4
30
1
4
30
-1.5
X
-1.0
2
1
4
10
1
4
10
-1.0
X
-0.5
3
1
4
7
1
4
7
-0.5
X
+1.0
4
4
4
4
4
4
4
+0.5
X
+1.0
5
6
6
1
6
6
1
+1.0
X
+1.5
6
9
7
1
9
8
1
+1.5
X
+2.5
7
15
7
1
16
8
1
X
+2.5
8
15
7
1
16
8
1
After the initial operation, the instructed frequency will change or shift from initial frequency according to the judgment on
temperature different from sampling (refer to the Table on Shifting Frequency Zone).
15
CS-E15CKP CU-E15CKP5
Содержание CS-E15CKP
Страница 8: ...4 Dimensions 8 CS E15CKP CU E15CKP5 ...
Страница 9: ...9 CS E15CKP CU E15CKP5 ...
Страница 10: ...5 Refrigeration Cycle Diagram 10 CS E15CKP CU E15CKP5 ...
Страница 11: ...6 Block Diagram 11 CS E15CKP CU E15CKP5 ...
Страница 12: ...7 Wiring Diagram 12 CS E15CKP CU E15CKP5 ...
Страница 39: ...IONIZE 42 43 44 41 39 CS E15CKP CU E15CKP5 ...
Страница 40: ...IONIZER IONIZER IONIZER IONIZER 40 CS E15CKP CU E15CKP5 ...
Страница 41: ...CZ SFD72P 41 CS E15CKP CU E15CKP5 ...
Страница 42: ...42 CS E15CKP CU E15CKP5 ...
Страница 43: ... H23 H27 H28 43 CS E15CKP CU E15CKP5 ...
Страница 44: ...44 CS E15CKP CU E15CKP5 ...
Страница 45: ...45 CS E15CKP CU E15CKP5 ...
Страница 75: ...13 Technical Data 75 CS E15CKP CU E15CKP5 ...
Страница 87: ...87 CS E15CKP CU E15CKP5 ...
Страница 88: ...How to use electronic circuit diagram 88 CS E15CKP CU E15CKP5 ...
Страница 89: ...18 1 REMOTE CONTROL 89 CS E15CKP CU E15CKP5 ...
Страница 90: ...18 2 PRINT PATTERN INDOOR UNIT PRINTED CIRCUIT BOARD 90 CS E15CKP CU E15CKP5 ...
Страница 91: ...18 3 PRINT PATTERN OUTDOOR UNIT PRINTED CIRCUIT BOARD VIEW 91 CS E15CKP CU E15CKP5 ...
Страница 92: ...92 CS E15CKP CU E15CKP5 ...
Страница 93: ...93 CS E15CKP CU E15CKP5 MAICO Printed in Malaysia ...
Страница 94: ......