13.6 Compressor Reverse Rotation Protection Control
•
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between
intake air and indoor heat exchanger is 2.5°C (cooling mode)/5°C (heating mode) or less for continuous 2
minutes, compressor will stop and restart automatically.
•
Time Delay Safety Control is activated before the compressor restart.
T = Intake air temperature - Indoor heat exchanger temperature
•
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
13.7 Dew Prevention Control
•
To prevent dew formation at indoor unit discharge area.
•
This control will be activated if:-
o
Cooling mode or Quiet mode.
o
Remote Control setting temperature is less than 25°C.
o
Fan speed is at CLo or QLo.
o
Room temperature is constant (±1°C) for 30 minutes.
o
Compressor is continuously running.
•
Fan speed and angle of horizontal louver (vertical airflow angle) will be adjusted accordingly in this control.
o
Fan speed will be increased slowly if the unit is in quiet mode but no change in normal cooling mode.
•
Dew prevention stop condition.
o
Remote control setting temperature is more than 25°C.
o
Fan speed is not set at CLo or QLo.
o
Select Powerful operation.
13.8 30 Minutes Time Save Control
•
The compressor will start automatically if it has stopped for 30 minutes and the intake air temperature falls
between the compressor OFF temperature and compressor ON temperature during the period.
•
This is to maintain the room temperature as set. Despite of this, it is to prevent a wrong judgement of intake air
temperature due to poor installation near the sensor area.
13.9 Compressor Overload Protection Control
Outdoor Fan Control
•
If the temperature of the indoor heat exchanger rises to 51°C, outdoor fan stops. The outdoor fan restarts when
the indoor heat exchanger temperature falls to 49°C.
Compressor high pressure protection
•
If the indoor heat exchanger becomes 65°C or more, the compressor will stop and restart automatically.
(Time Delay Safety Control - 4 minutes waiting).
•
This is to reduce the pressure, as to reduce the indoor heat exchanger temp. Nevertheless, is to protect the
compressor from overload of too high temperature.
13.10 4-Way Valve Control
•
4-way valve always on during Heating operation. (except deicing operation)
•
When the unit is switched off by remote control during Heating operation, the 4-way valve stay at Heating
position for 5 minutes.
•
This is to prevent the refrigerant flow process sound for being occur.
Содержание CS-A12KKD-2
Страница 3: ...3 18 Exploded View and Replacement Parts List 125 18 1 Indoor Unit 125 18 2 Outdoor Unit 131 ...
Страница 16: ...16 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 17: ...17 5 Dimensions 5 1 Indoor Unit 5 1 1 CS A9KKD 2 CS A12KKD 2 ...
Страница 18: ...18 5 1 2 CS A18KKD 2 CS A24KKD 2 CS A28KKD 2 ...
Страница 19: ...19 5 2 Outdoor Unit 5 2 1 CU A9KKD 2 5 2 2 CU A12KKD 2 ...
Страница 20: ...20 5 2 3 CU A18KKD 2 CU A24KKD 2 CU A28KKD 2 ...
Страница 21: ...21 6 Refrigeration Cycle Diagram 6 1 CS A9KKD 2 CU A9KKD 2 CS A12KKD 2 CU A12KKD 2 ...
Страница 22: ...22 6 2 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 CS A28KKD 2 CU A28KKD 2 ...
Страница 23: ...23 7 Block Diagram 7 1 CS A9KKD 2 CU A9KKD 2 ...
Страница 24: ...24 7 2 CS A12KKD 2 CU A12KKD 2 ...
Страница 25: ...25 7 3 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 ...
Страница 26: ...26 7 4 CS A28KKD 2 CU A28KKD 2 ...
Страница 31: ...31 9 Electronic Circuit Diagram 9 1 CS A9KKD 2 CU A9KKD 2 ...
Страница 32: ...32 9 2 CS A12KKD 2 CU A12KKD 2 ...
Страница 33: ...33 9 3 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 ...
Страница 34: ...34 9 4 CS A28KKD 2 CU A28KKD 2 ...
Страница 36: ...36 10 1 1 2 CS A28KKD 2 ...
Страница 39: ...39 10 1 7 Eco Patrol Printed Circuit Board ...
Страница 54: ...54 12 3 2 Soft Dry Operation Time Diagram For CS A18KKD 2 CU A18KKD 2 and CS A24KKD 2 CU A24KKD 2 ...
Страница 86: ...86 Normal Deice Time Diagram Overload Deice Time Diagram ...
Страница 91: ...91 a Normal Deice Time Diagram b Overload Deice Time Diagram ...
Страница 97: ...97 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Страница 99: ...99 Figure 10 Figure 11 ...
Страница 101: ...101 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Страница 103: ...103 Figure 21 Figure 22 Figure 23 ...
Страница 104: ...104 17 Technical Data 17 1 Thermostat Characteristics ...