(Heating Operation Condition)
•
When the piping air temperature reaches 38°C, the louver is changed from upper to lower limit. When the piping
air temperature falls 35°C, the louver is changed from lower to upper limit.
For CS-A9KKD-2 and CS-A12KKD-2
For CS-A18KKD-2 and CS-A24KKD-2
For CS-A28KKD-2
12.7.2 Manual
Control
•
When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and
the airflow direction louver move up and down in the range shown in the diagram.
•
The louver can be adjusted by pressing the button to the desired louver position.
•
When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.
51°
Closing
position
/ 135°
Lower limit for heating mode/62°
Horizontal
Upper limit/11°
43°
Closing
position
/ 148°
Lower limit for heating mode/43°
Horizontal
Upper limit/0°
43°
Closing
position
/ 133°
Lower limit for heating mode/52°
Horizontal
Upper limit/0°
Содержание CS-A12KKD-2
Страница 3: ...3 18 Exploded View and Replacement Parts List 125 18 1 Indoor Unit 125 18 2 Outdoor Unit 131 ...
Страница 16: ...16 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 17: ...17 5 Dimensions 5 1 Indoor Unit 5 1 1 CS A9KKD 2 CS A12KKD 2 ...
Страница 18: ...18 5 1 2 CS A18KKD 2 CS A24KKD 2 CS A28KKD 2 ...
Страница 19: ...19 5 2 Outdoor Unit 5 2 1 CU A9KKD 2 5 2 2 CU A12KKD 2 ...
Страница 20: ...20 5 2 3 CU A18KKD 2 CU A24KKD 2 CU A28KKD 2 ...
Страница 21: ...21 6 Refrigeration Cycle Diagram 6 1 CS A9KKD 2 CU A9KKD 2 CS A12KKD 2 CU A12KKD 2 ...
Страница 22: ...22 6 2 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 CS A28KKD 2 CU A28KKD 2 ...
Страница 23: ...23 7 Block Diagram 7 1 CS A9KKD 2 CU A9KKD 2 ...
Страница 24: ...24 7 2 CS A12KKD 2 CU A12KKD 2 ...
Страница 25: ...25 7 3 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 ...
Страница 26: ...26 7 4 CS A28KKD 2 CU A28KKD 2 ...
Страница 31: ...31 9 Electronic Circuit Diagram 9 1 CS A9KKD 2 CU A9KKD 2 ...
Страница 32: ...32 9 2 CS A12KKD 2 CU A12KKD 2 ...
Страница 33: ...33 9 3 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 ...
Страница 34: ...34 9 4 CS A28KKD 2 CU A28KKD 2 ...
Страница 36: ...36 10 1 1 2 CS A28KKD 2 ...
Страница 39: ...39 10 1 7 Eco Patrol Printed Circuit Board ...
Страница 54: ...54 12 3 2 Soft Dry Operation Time Diagram For CS A18KKD 2 CU A18KKD 2 and CS A24KKD 2 CU A24KKD 2 ...
Страница 86: ...86 Normal Deice Time Diagram Overload Deice Time Diagram ...
Страница 91: ...91 a Normal Deice Time Diagram b Overload Deice Time Diagram ...
Страница 97: ...97 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Страница 99: ...99 Figure 10 Figure 11 ...
Страница 101: ...101 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Страница 103: ...103 Figure 21 Figure 22 Figure 23 ...
Страница 104: ...104 17 Technical Data 17 1 Thermostat Characteristics ...