e-ion
Check
Mode
o
e-ion abnormality check mode
o
Purpose is to improve sensor serviceability when sensor is malfunction.
(1) Control starting condition
When all of the conditions are formed
Not in Patrol Demo mode.
e-ion operation ON.
When e-ion check mode signal is received; the procedure of selection is as shown:
•
Press “Set” button continuously for 15 seconds by using pointer to enter internal setting mode.
•
Press “Timer Decrement" button to select “CHC”.
•
Confirm setting by pressing “Timer Set” button, a “beep” sound will be heard.
SET
SET
Transmit Patrol default OFF/ON code
(Buzzer: OFF:Long Beep, ON:Short Beep)
Press continously for 15s
SET
Transmit Patrol demo code
(Buzzer: OFF:Long Beep, ON:Short Beep)
SET
Transmit ECO demo code
(Buzzer: OFF:Long Beep, ON:Short Beep)
SET
Transmit check code
(Buzzer:Short Beep)
o
If abnormal discharge is detected at filter (short-circuited) due to water or dust adhesion, etc., the e-ion
indicator blinks immediately.
Содержание CS-A12KKD-2
Страница 3: ...3 18 Exploded View and Replacement Parts List 125 18 1 Indoor Unit 125 18 2 Outdoor Unit 131 ...
Страница 16: ...16 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Страница 17: ...17 5 Dimensions 5 1 Indoor Unit 5 1 1 CS A9KKD 2 CS A12KKD 2 ...
Страница 18: ...18 5 1 2 CS A18KKD 2 CS A24KKD 2 CS A28KKD 2 ...
Страница 19: ...19 5 2 Outdoor Unit 5 2 1 CU A9KKD 2 5 2 2 CU A12KKD 2 ...
Страница 20: ...20 5 2 3 CU A18KKD 2 CU A24KKD 2 CU A28KKD 2 ...
Страница 21: ...21 6 Refrigeration Cycle Diagram 6 1 CS A9KKD 2 CU A9KKD 2 CS A12KKD 2 CU A12KKD 2 ...
Страница 22: ...22 6 2 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 CS A28KKD 2 CU A28KKD 2 ...
Страница 23: ...23 7 Block Diagram 7 1 CS A9KKD 2 CU A9KKD 2 ...
Страница 24: ...24 7 2 CS A12KKD 2 CU A12KKD 2 ...
Страница 25: ...25 7 3 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 ...
Страница 26: ...26 7 4 CS A28KKD 2 CU A28KKD 2 ...
Страница 31: ...31 9 Electronic Circuit Diagram 9 1 CS A9KKD 2 CU A9KKD 2 ...
Страница 32: ...32 9 2 CS A12KKD 2 CU A12KKD 2 ...
Страница 33: ...33 9 3 CS A18KKD 2 CU A18KKD 2 CS A24KKD 2 CU A24KKD 2 ...
Страница 34: ...34 9 4 CS A28KKD 2 CU A28KKD 2 ...
Страница 36: ...36 10 1 1 2 CS A28KKD 2 ...
Страница 39: ...39 10 1 7 Eco Patrol Printed Circuit Board ...
Страница 54: ...54 12 3 2 Soft Dry Operation Time Diagram For CS A18KKD 2 CU A18KKD 2 and CS A24KKD 2 CU A24KKD 2 ...
Страница 86: ...86 Normal Deice Time Diagram Overload Deice Time Diagram ...
Страница 91: ...91 a Normal Deice Time Diagram b Overload Deice Time Diagram ...
Страница 97: ...97 Figure 3 Figure 4 Figure 5 16 1 1 3 To remove discharge grille Figure 6 ...
Страница 99: ...99 Figure 10 Figure 11 ...
Страница 101: ...101 16 2 1 3 To remove power electronic controller Figure 14 Figure 15 Figure 16 Figure 17 ...
Страница 103: ...103 Figure 21 Figure 22 Figure 23 ...
Страница 104: ...104 17 Technical Data 17 1 Thermostat Characteristics ...