4-302
2WAY SYSTEM Unit Specifi cations
1
2
3
4
5
6
7
8
9
17. Slim Low Static Ducted Type (M1 Type)
Indoor unit (C)
MODEL No.
S-28MM1E5
Power source
220 - 230 - 240 V, single-phase, 50/60 Hz
Controller P.C.B. Ass'y
CB-US075XH (Microprocessor)
Fan (Number...diameter)
mm
Centrifugal (1...ø190)
Fan motor
Model...Nominal output
W
DK8-63G280H...60 W
Power source
280 / 340 VDC / 3 phase / 50 Hz
No. of pole...r.p.m. (230V, High)
rpm
8P... 834
Coil resistance
(Ambient temperature 20°C)
Ω
–
Run capacitor
VAC, µF
–
Electronic expansion valve
Coil
UKV-U032E
Coil resistance (at 20°C)
Ω
ORG – GRY : 46
YEL – GRY : 46
RED – GRY : 46
BLK – GRY : 46
Valve body
UKV-18D31
Heat exchanger
Coil
Aluminium plate fin / Copper tube
Rows...fi n pitch
mm
3...1.4
Face area
m
2
0.128
Drain pump
PLD-12230ST-2
Rated
V, W
AC 230 V, 50 Hz, 12 W
Height from unit bottom & capacity
850 mm, 400 cc/min
TD831159-04̲2WAY VRF.indb 302
TD831159-04̲2WAY VRF.indb 302
2014/09/08 12:02:50