4-297
2WAY SYSTEM Unit Specifi cations
1
2
3
4
5
6
7
8
9
17. Slim Low Static Ducted Type (M1 Type)
Unit specifi cations (D)
MODEL No.
Indoor Unit
S-36MM1E5
POWER SOURCE
220 - 230 - 240 V, single-phase, 50/60 Hz
PERFORMANCE
Cooling
Heating
Capacity
kW
3.6
4.2
BTU / h
12,000
14,000
Air circulation (Hi / Me / Lo)
m
3
/ h
540 / 480 / 420
Moisture removal (High)
Liters / h
1.2
–
External static pressure (High)
Pa {mmAq}
15 {1.5}: At shipment 40 {4.1}: Using short circuit connection
ELECTRICAL RATINGS
Voltage rating
V
220
230
240
220
230
240
Available voltage range
V
198 - 264
198 - 264
Running amperes
A
0.31
0.31
0.31
0.28
0.28
0.28
Power input
W
42
42
42
32
32
32
Power factor
%
62
59
56
52
50
48
Max. starting amperes
A
–
–
–
–
–
–
FEATURES
Controls
Microprocessor
Timer
ON / OFF Timer (Max. 72 h)
Fan speeds
3 and Automatic control
Air fi lter
Washable, easy access
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
32 / 30 / 28
Using short circuit connection (Hi / Me / Lo)
dB-A
34 / 32 / 30
Refrigerant tubing connections
Flare type
Refrigerant tube
diameter
Liquid tube
mm (in.)
6.35 (1 / 4)
Gas tube
mm (in.)
12.7 (1 / 2)
Drain connection
OD26 mm
Drain pump
Max. head 500 mm above drain connection
Remote controller
Optional (Wired / Wireless)
Refrigerant tubing kit / Accessories
–
Color (Approximate value)
–
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height
mm (in.)
200 (7-7 / 8)
220 (8-21 / 32)
Width
mm (in.)
750 (29-17 / 32)
1030 (40-35 / 64)
Depth
mm (in.)
640 (25-13 / 64)
745 (29-21 / 64)
Net weight
k
g
(lbs.)
19 (42)
Shipping weight
k
g
(lbs.)
23 (51)
Shipping volume
m
3
(cu.ft)
0.169 (5.97)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27°C DB / 19°C WB; Outdoor air temperature 35°C DB
Heating: Indoor air temperature 20°C DB; Outdoor air temperature 7°C DB / 6°C WB
TD831159-04̲2WAY VRF.indb 297
TD831159-04̲2WAY VRF.indb 297
2014/09/08 12:02:49
2014/09/08 12:02:49