RS232 Communications Protocol & Command Set 

(continued)

14

USA & Canada (800) 472-5555  •  (707) 283-5900  •  Fax (707) 283-5901

Non Critical Load Outlets On

This command controls the relay that feeds power to the NCL Outlets.
Note that if the MAIN relay is off, the outlets will still be un-energized.

Send to UPS:

NCL_ON<CR>

Action:

NCL relay closes.

Response from UPS:

NCL_OUTLETS_ON<CR> (if MAIN 
relay is ON)

NCL_OUTLETS_OFF<CR> (if MAIN 
relay is OFF)

Non Critical Outlets Off

Send to UPS:

NCL_OFF<CR>

Action:

NCL relay opens.

Response from UPS:

NCL_OUTLETS_OFF<CR>

Set Low Battery NCL (Non-Critical Load) Shutoff 

It is desirable to allow the user to set the battery storage threshold in
which the non-critical load outlets will shut off therefore reserving the
remaining battery charge for the critical equipment.  If the battery
charge falls below the threshold, Non Critical Load Outlets are turned
OFF.

A common example of critical equipment would be a projector.  It is
critical that power be maintained to a projector to allow its fan to run
and cool the bulb.  If the bulb is allowed to overheat, it will be damaged
and is very expensive to replace.

Send to UPS:

BATTHRESH<SP>XX<CR>

<SP> represents a space: 20 Hex

XX is a number between 25 and 60 
represented in ASCII.

If XX is a valid number, between 25 and 60:

Action:

Assigns the battery threshold variable 
with the value XX

Response from UPS:

BTHRESH<SP>XX<CR>

If XX is not valid:

Action:

None

Response from UPS:

INVALIDCMD<CR>

Enable Audible Alarm 

It is important that the UPS be as quiet as possible as it will be located
in a home theater environment.  It is desirable to control the warning
beeper.  The default setting for the alarm is OFF.

Send to UPS:

BEEPON<CR>

Action:

The beeper will sound when running 
from battery.

Response from UPS:

BEEPISON<CR>

Disable Warning Beeper

Send to UPS:

BEEPOFF<CR>

Action:

The beeper will not sound when running 
from battery.

Response from UPS:

BEEPISOFF<CR>

Restore Default Settings

Send to UPS:

RESTORE<CR>

Action:

Set Non-critical load threshold (2.5) 
to 66%

Disable the warning beeper (2.7)

Set High Voltage Failure Threshold to 
147V (2.8)

Set Low Voltage Failure Threshold to 
88V (2.9)

Set Battery Mode Voltage to 120V (2.10)

Response from UPS:

DEFAULTSRESTORED<CR>

QUERIES
Request Outlet Status

Transmit the ON/OFF status of the outlet banks.

Send to UPS:

?OUTLETSTAT<CR>

If NCL Outlets are ON:

Response from UPS:

NCL_OUTLETS_ON<CR>

If NCL Outlets are OFF:

Response from UPS:

NCL_OUTLETS_OFF<CR>

If CL Outlets are ON:

Response from UPS:

CL_OUTLETS_ON<CR>

If CL Outlets are OFF:

Response from UPS:

CL_OUTLETS_OFF<CR>

Содержание PFPower M1500-UPS-PFP

Страница 1: ...Cinema UPS Owner s Manual 1690 Corporate Circle Petaluma CA 94954 www panamax com M1500 UPS PFP The M1500 UPS PFP is a Programmable Uninterruptible Power Supply Voltage Regulator Power Conditioner Pat...

Страница 2: ...Battery Features pgs 10 11 Diagnostics pg 11 Troubleshooting pg 12 Technical Specifications pg 12 RS232 Communications Protocol Command Set pgs 13 14 15 16 FCC Notice and Warranties Pg 17 Table of Co...

Страница 3: ...e battery can energize hazardous live parts inside even when the AC input power is disconnected CAUTION To prevent the risk of fire or electric shock install in a temperature and humidity controlled i...

Страница 4: ...eptacle wall outlet Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not service equipment with large electri cal demands e g refrigerator copier etc Avoid using ext...

Страница 5: ...dication of the battery charge If battery capac ity is under 25 no indicator LED will illuminate and UPS starts beeping if the audible alarm is enabled 3 USA Canada 800 472 5555 707 283 5900 Fax 707 2...

Страница 6: ...t to both outputs The IR LED s will flash once per second during the delay time and will stop flashing after the IR code is sent 2 If the delay settings are the same for both IR1 and IR2 the IR2 code...

Страница 7: ...d Home Cinema Power Control Software The M1500 UPS PFP has one rear panel serial port that provides the ability to program special functions safely shutdown a home theater PC HTPC or integrate the UPS...

Страница 8: ...mand 12 Follow the on screen instructions 13 Once the software has finished installing remove the disk and restart your computer For Windows NT 4 0 1 Click on Start point to Settings then click Contro...

Страница 9: ...n the HTPC during extended power fail ures This requires a permanent RS232 connection to the HTPC and having the Home Cinema Power Control software running in the background on the HTPC When a power f...

Страница 10: ...for the UPS software 12 Time between power failure and shutdown For use with an HTPC This is the user controllable delay between when the power fails and the software starts the shutdown process If u...

Страница 11: ...tes and times of any scheduled startups and shut downs 7 Delete Clears the selected item from the schedule 3 Turn Off Select the day date and time that you want the computer system to shutdown This is...

Страница 12: ...M1500 UPS PFP 3 year warranty PF Power will replace M1500 UPS PFP batteries if the fail within the 3 year product warranty period For battery replacement information and instructions please contact Pa...

Страница 13: ...boost 13 of input voltage for output regulation while input voltage is from 8 to 15 under nominal AVR Max boost 26 of input voltage for output regulation while input voltage is from 15 to 26 under nom...

Страница 14: ..._____________________________Yes Maintenance free____________________________________________________________Yes Lead acid___________________________________________________________________Yes User re...

Страница 15: ...he battery charge falls below a set threshold refer 2 5 It is desirable to have the ability to switch the power to the outlets on and off to force a hard reboot of equipment Devices such as satellite...

Страница 16: ...pace 20 Hex XX is a number between 25 and 60 represented in ASCII If XX is a valid number between 25 and 60 Action Assigns the battery threshold variable with the value XX Response from UPS BTHRESH SP...

Страница 17: ...is in AVR mode and bucking voltage by 11 Response from UPS AVRBUCK1 CR If the UPS is in BATTERY mode Response from UPS BATTERY CR Request Load Level Status Transmit the load level percentage Send to U...

Страница 18: ...n AVR or BATTERY mode UPS is in AVR boosting 13 UPS is in AVR boosting 26 UPS is in AVR bucking 15 UPS is in BATTERY mode Battery charge falls below critical load threshold Input voltage exceeds high...

Страница 19: ...of three 3 years from the date of purchase that the unit shall be free of defects in design materi al or workmanship and Panamax will repair or replace any defective unit Upgrade Policy Valid only in...

Страница 20: ...1690 Corporate Circle Petaluma CA 94954 Tel 707 283 5900 Fax 707 283 5901 www panamax com...

Отзывы: