General
The heat pump must not be connected without the permission of the electricity supplier and must be
connected under the supervision of a qualified electrician.
The heat pump does not include an isolator switch on the incoming electrical supply. The power supply
cable must be connected to a circuit-breaker with at least a 3 mm breaking gap. Incoming supply must
comply with the technical requirements, with ground wire, via a distribution board with fuses.
Note!
Electrical installation and service must be carried
out under the supervision of a qualified electrician.
Electrical installation and wiring must be carried
out in accordance with the stipulations in force.
Wires, spare parts and materials etc. must satisfy the relevant standards issued by the host country or region.
Isolator switch
If an insulation test is to be carried out in the building, please make sure to disconnect the heat pump.
To avoid the possibility of false action caused by electromagnetic coupling, the communication wire must
2
be STP(Shielded Twisted Pair). The size of communication wire should not less than 0.5mm .
Electric connection