Installation position
Installation in exceptional circumstances(unit:mm)
6
The unit must be installed upon reliable machine base or framework. Weight capacity of framework should be 3
times of the body weight, and safeguard measures should be taken to avoid malfunction of fastenings.
4 Ensure the unit is well ventilated, direction of air exhaust is kept away from windows of neighboring buildings, and
the exhaust air cannot flow back. moreover, adequate service clearance should be kept around the unit.
5 The unit should not be installed at places accompanied with oil, inflammable gases, corrosive components e.g.
sulfur compound, or high-frequency equipment.
1 If the unit is to be installed on the floor, its undercarriage should be heightened, to avoid ingression of accumulated
water in rainy season. In snowy areas, it is important to prevent accumulated snow from blocking up the air-out. The
recommended height is 20cm to 30cm.
2 Drain ditch or other facilities should be arranged under the outdoor unit,
to avoid the environment influence
because of water discharge.
3 To install the unit at balcony or top of building, the installation site must meet the allowable bearing capacity of
building structure, without affecting the structural safety.
7 The unit should not be installed at sites with typhoon/ earthquake hazards. Midair installation should be
avoided as much as possible, for machine falling may result in severe accident.
Installation must be carried out by professional
personnel.
No obstacle in front of the unit
200
200
3
5
0
Outdoor unit
5
0
0
350
Obstacle above the unit
Note!
1
0
0
0
Obstacle in front of the unit
Several units in a row
Outdoor unit
400
200
3
5
0
Outdoor unit
Outdoor unit
Outdoor unit
16
5.Installation