ENGLISH
6.2
FAN MENU
Through this Menu you can select the Fan speed.
Pressing the keys
K3
and
K4
it is possible to see and modify on the Display the speed currently selected for the Fan
(LED
flashes).
MANUAL MODE
: You can turn off the Fan by setting the speed
P0
, or by selecting a speed from
P1
(minimum speed)
to
P10
(maximum speed).
AUTOMATIC MODE
: You cannot turn off the Fan, you can select a speed from
P1
(minimum speed) to
P10
(maximum speed).
PROPORTIONAL MODE
: it is not possible to switch off the Fan nor to set a speed, it is only possible to see the speed
selected by the temperature control unit.
Press the
K2
key to save the new value or wait 5 seconds.
Press the
K1
key to exit without saving.
6.3
INSTALLER MENU
Access to this Menu is the RESPONSIBILITY of INSTALLATION TECHNICIANS or EXPERT PERSONNEL
,
because the parameters shown, if modified, may render the product is not suitable for the application in use.
To access the MENU
simultaneously
press the keys
K2
and
K4
for about 3 seconds.
To scroll through the parameters, use the keys
K3
and
K4
To view the value of the parameter and enter for modification, press the key
K2
To change the value, press the keys
K3
and
K4
To save the new value, press the key
K2
.
To exit without saving, press the key
K1
Press the
K1
key again to exit from the Menu or wait 60 seconds
Description
Code
Min
Set
Max
U.O.M.
Fan Activation Air Thermostat
E01
30
50
100
[°C]
SAFETY Air Thermostat
E02
80
100
140
[°C]
ALARM Air Thermostat
E03
100
130
180
[°C]
FAN SAFETY Air Thermostat
E04
100
145
180
[°C]
Valve Opening Air Thermostat
E05
20
30
140
[°C]
Valve Closing Air Thermostat
E06
20
80
140
[°C]
SERVICE output Fan Activation Air Thermostat
E07
20
50
180
[°C]
Temperature Range for Proportional operation
E50
20
45
100
[°C]
Fan Activation hysteresis thermostat
IE01
1
2
40
[°C]
SAFETY hysteresis thermostat
IE02
1
2
40
[°C]
ALARM hysteresis thermostat
IE03
1
2
40
[°C]
FAN SAFETY hysteresis thermostat
IE04
1
2
40
[°C]
Opening Valve hysteresis thermostat
IE05
1
2
40
[°C]
Closing Valve hysteresis thermostat
IE06
1
2
40
[°C]
SERVICE output Activation hysteresis thermostat
IE07
1
2
40
[°C]
Room temperature hysteresis thermostat
Ib01
0
1
20
[°C]
Fan Speed P01 (minimum)
UA01
0
30
100
[%]
Fan Speed P09 (ninth)
UA09
0
70
100
[%]
Fan Speed P10 (maximum)
UA10
0
100
100
[%]
Delay Time Damper Closing
t 06
0
10
120
[min]
Time of suspension of Acoustic alarm
t 07
1
5
60
[min]
Time of Fan Starting
t 08
0
0
10
[sec]
Input Configuration S2; 0 = not used; 1 = Probe; 2 = Thermostat
P01
0
0
2
n
SERVICE Output Configuration
P02
0
0
3
n
Enabling FAN SAFETY
P03
0
0
1
n
Enabling Air SAFETY
P04
0
1
1
n
Enabling Air ALARM
P05
0
1
1
n
Enabling Damper Start Function
P12
0
0
1
n
Input Configuration S2; 1 = Probe; 2 = Thermostat
P17
1
1
2
n
NOTES:
Modifying
UA01
,
UA09
,
UA10
, the Fan immediately goes to the speed that you are calibrating in order to see the effect.
6.4
S1 INPUT CONFIGURATION ERROR
There may be two error conditions in the configuration of the product:
A.
P17
= 1
st input
Thermostat
When the fire is off it will display the writing
Lo
When the stove is on it shows
Hi
with the acoustic indicator in operation.
B.
P17 = 2
nd input
Probe NT100K
.
By powering the control unit,
Err
will appear on the display.