11
GHI
Type infrared ceramic heaters
User’s Manual
L
N
5
10
8
9
16
18
VK4125
ION
IGN
If You followed the above instructions, and the appliance is assembled, installed and electronically connected to the power line, then
the following final control is recommended. Check the surface for any kind of damages of the protective gride, the ceramic. Check the
fittings of the gas ramp and its connections, and the ignition electrode for any kind of abnormalities. At the ignition electrode check the
distance to the ceramic surface and to the protective grid. Furthermore if it is necessary adjust again the desired maximum 4 mm value
to the ceramic. Electrodes must not be closer than 10 mm to the protective grid and must not reach the surface of ceramics.
Electrical connection scheme of HONEYWELL S4965R2027 type automatic burner
control
7. picture: Connection points of S4965R2027 automatic burner control
Recommended temperature controllers for the appliance (these can be purchased at the appliance manufacturer)
8.picture: Temperature controller
Temperature sensor
Optional accessories
Thermostat
FP-1D typed thermostat
FP- 4D typed thermostat
(programmable)