17
ACR
air curtains
Operation and Maintenance Documentation
10.
OPERATION AND MAINTENANCE
The engine and fan of the ACR air curtains are maintenance-free devices but regular check-ups are advised, especially motor and
bearing (fan’s rotor should rotate freely, free from any axial and radial throws/run-outs and undesired knocks/rattles.
The heat exchanger requires systematic cleaning of all dirts /impurities off. Before the start of the heating period, the heat exchanger is
advised to be cleaned with compressed air directed to the air outlets; there is no need for dismantling of the device.
Pay special attention when cleaning the exchanger’s fin due to high possibility of damaging them. If the fin is bent use a special tool. If
the device has not been used for a longer period of time, unplug it before the next use.
The heat exchanger is not equipped with any fire protection device. The heat exchanger may be damaged if the room temperature
goes below 0°C; anti-freeze liquid must be added to the water circulation/system. Anti-freeze liquid must be appropriate for the material
the exchanger is made of (copper) as well as other elements of the hydraulic system/circulation. The liquid must be diluted with water
accordingly to the manufacturer’s recommendation.
NOTICE !
• Any and all repair and maintenance works must be conducted with the power off and the heat input
disconnected.
• Only suitably qualified staff well acquainted with the safety regulations concerning handling with an
electrical device must be employed when the device is being installed, started and operated
• In the event of coolant leak, when the water system is under pressure, any repairs of the leakage are
strictly prohibited.
• Any repairs of the device must be conducted only if the device is disconnected from the power supply.
• If the device being operated gives metallic clatter, vibration or the level of noise is increasing, check
if the mounting of the fan has not become loose – in case of any problems contact the installer of the
device or Distributor’s Authorized Service immediately.
11.
TROUBLESHOOTING AND TECHNICAL PROBLEMS
Possible problems and solutions are shown below. To eliminate a problem encountered contact the authorized service.
Fault, symptoms
Potential causes
Solutions
No heating, fan not operating
No power supply
Check the power switch Check the
power supply Check the power cable – if it is dam-
aged - replace the cable
Damage to the fan
Replace the motor
Damage to the switches on control panel
Check the switches – if are damaged – replace
Heating medium leakage
•
leakage on joints with hot water supply system
•
leakage in collector
Loss of tightness
Sealing supply system; repairing the heat exchanger
Heat output drop
Temperature of the heating medium differs
from the required one Contaminated heat
exchanger’s surface
Restore the temperature of the heating medium
Clean the surface of the heat exchanger
Содержание ACR 1000W
Страница 19: ......