ADF SERIES™ OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
ADF Series Power Source Operation Manual
Page 216 of 349
Command Syntax
[SOURce:]KVA:LIMit#
Description
This command sets the programmable apparent power limit level in
kVA for phase #. If # is omitted, all available phases are set to the
value specified. The max available apparent power for a phase can be
obtained using the [SOURce:]KVA:LIMit#:MAX? query command.
Parameters
Limit value in kVA
Parameter Format
<nr2>
Example
KVA:LIM 2.5
Query Format
[SOURce:]KVA:LIMit#?
Returned Data Format
<nr2>
Query Example
POW:LIM1?
2.5000
Query Format
[SOURce:]KVA:LIMit#:MAX?
Description
Returns maximum available apparent power capability for the
specified phase # in kVA. If # is omitted, returns maximum available
apparent power level for last phase selected. Typically, this value will
be the same for all phases.
Returned Data Format
<nr2>
Query Example
KVA:LIM1:MAX?
5.0000
Query Format
[SOURce:]MODE#?
Description
Returns protection mode for the selected phase # (# = 1, 2, or 3). If #
is omitted, returns protection mode for all phases in comma
separated format.
Note: When the phase suffix is 1, 2 or 3 the possible return
categories are from 0 to 4. With suffix is omitted, this command will
return MIXED(5) if modes for each phase are not the same.
For example, if in split phase mode phase A (suffix 1) is in VOLTAGE
mode but phase B (suffix 2) is in CURRENT mode, the query
SOUR:MODE? you will return MIXED:
SOUR:MODE1? = VOLTAGE and SOUR:MODE2? = CURRENT ->
SOUR:MODE? = MIXED
If both or phases are set to the same mode, the actual mode will be
returned:
SOUR:MODE1? = VOLTAGE and SOUR:MODE2? = VOLTAGE ->
SOUR:MODE? = VOLTAGE
Returned Data Format
<cr>
Available protection modes:
0 = NONE
1 = VOLTAGE
2 = CURRENT
3 = POWER
4 = KVA
5 = MIXED
Query Example
SOUR:MODE?
VOLTAGE, VOLTAGE, VOLTAGE