ADF SERIES™ OPERATION MANUAL
Rear Panel, Connectors and Protection
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
ADF Series Power Source Operation Manual
Page 137 of 349
7
Rear Panel, Connectors and Protection
This section describes the rear panel layout of the ADF Series® AC power source.
7.1
OUTPUT Terminals
WARNING
HAZARDOUS OUTPUT: The power source output may be set to hazardous voltage levels. It
provides basic isolation from the AC input mains. Therefore, the output must always be
considered hazardous. Connections must be inaccessible to the operator in all situations when
AC input mains voltage is applied.
Always disconnect power supply from the mains before connecting or disconnecting to the
hazardous output terminals.
AVERTISSEMENT
SORTIE DANGEREUSE: La sortie de l´appareil peut être réglée à des niveaux de tension dangereux.
L´appareil fournit une isolation de base du réseau d'entrée AC. Par conséquent, la sortie doit
toujours être considérée comme dangereuse. Les connexions doivent être inaccessibles à
l'opérateur dans toutes les situations où la tension d´entrée secteur est appliquée.
Toujours débrancher l'alimentation secteur avant de connecter ou déconnecter les bornes de
sortie dangereuses.
The output terminal block for load connections is located near the center of the rear panel.
Note:
Always refer to Section 2.3 “Safety Information” before making any load connections.
7.1.1
Output Power Connector Rating and Isolation
Maximum rated output voltage:
300V rms AC, 425Vdc
Maximum Current Rating:
60A
Connector Type:
Phoenix Contact SPC 16/ 6-STF-10, 16 - 1711417
Designated Use:
AC Load Connection
Isolation Rating:
600V
Wire Stripping Length:
18 mm