Pacific energy SUPER 27 Скачать руководство пользователя страница 17

Through Wall Installations 

(as per NFPA 211-2013)

ATTENTION: VAPOUR BARRIER MUST BE  MAINTAINED WHEREVER CHIMNEY OR OTHER 
COMPONENTS PENETRATE TO THE EXTERIOR OF THE STRUCTURE. SEE LOCAL BUILDING CODES 
FOR PROPER AND APPROVED METHODS OF MAINTAINING VAPOUR BARRIER.

Minimum Clearance 12 in. (305mm) to combustibles 

System A. Minimum 3.5 in. (90 mm) thick brick masonry wall framed into combustible wall with a minimum 
of 12 in. (305 mm) brick separation from clay liner to combustibles. Fireclay liner (ASTM C 315, Standard 
Specifications for Clay Fire Linings, or equivalent), minimum 5/8 in. (16 mm) wall thickness, shall run from 
outer surface of brick wall to, but not beyond, the inner surface of chimney flue liner and shall be firmly 
cemented in place. 

Minimum Clearance 9 in. (229mm) to combustibles 

System B. Solid-Insulated, listed factory-built chimney length of the same inside diameter as the chimney 
connector and having 1 in. (25.4 mm) or more of insulation with a minimum 9 in. (229 mm) air space between 
the outer wall of the chimney length and combustibles.

The inner end of the chimney length shall be flush with the inside of the masonry chimney flue and shall be 
sealed to the flue and to the brick masonry penetration with non-water-soluble refractory cement. Supports 
shall be securely fastened to wall surfaces on all sides.

Fasteners between supports and the chimney length shall not penetrate the chimney liner. 

SYSTEM A   

Minimum 12” (305 mm) 
to combustibles

Minimum chimney clearance
to brick and combustibles
2” (51 mm). 

Minimum clearance
12” (305 mm) of brick 

Chimney connector

Fireclay liner

Masonry chimney
constructed to NFPA 211 

C

hi

m

ne

flu

e

Figure 11:  System A.ai

  

SYSTEM B   

Minimum chimney clearance
from masonry to sheet steel 
supports and combustibles 
2” (51 mm)

Factory built 
chimney length

Solid-insulated, listed 
factory built chimney 
length

Chimney length 
flush with inside 
of flue

Air space: 
9” (229 mm) min.

Sheet steel supports

Masonry chimney
constructed to NFPA 211 

Chimney 
flue

Minimum clearance
9” (229 mm)

Use chimney 
manufacturers’ parts to 
attach connector 
securely 

Chimney connector

Nonsoluble 
refractory 
cement

Figure 12:  System B.ai

SUPER / CLASSIC_030818-32

17

100000813

Содержание SUPER 27

Страница 1: ...tions Contact local building or fire officials about restrictions and installation inspection requirements in your area Meets the Environmental Protection Agency s May 2015 Particulate Emission Standa...

Страница 2: ...ble Wall Connector 14 Single Wall Connector 14 Through Wall Installations 17 Mobile Home Installation 19 Procedure 19 Combustion Air 20 Operation 21 Over Firing 21 Wood Selection 21 DO NOT BURN 21 How...

Страница 3: ...X RESTRICTIONS PERMIS D INSTALLATION ET INSPECTIONS DANS VOTRE R GION NE RELIEZ PAS CET APPAREIL UN CONDUIT DE CHEMIN E DESSERVANT D J UN AUTRE APPAREIL TATS UNIS SEULE MENT UTILISEZ UN RACCORDEMENT N...

Страница 4: ...uilding up at least as quickly in the chimney WARNING ONLY USE MATERIALS SUPPLIED BY MANUFACTURER WHEN DOING MAINTENANCE OR REPLACEMENTS 4 DOOR GASKETS The gasket used by Pacific Energy 7 8 22mm mediu...

Страница 5: ...difficult for the tars and gases to ignite thus creating dense smoke and poor com bustion This moisture laden smoke cools the chimney compounding the problem by offering the smoke the ideal place to c...

Страница 6: ...dle a chimney fire 4 After the chimney fire is out the chimney must be cleaned and checked for stress and cracks before start ing another fire Also check combustibles around the chimney and the roof T...

Страница 7: ...p heat shield and mounting bolt Baffle Gasket Brick Rails Manifold Blower The blower should be cleaned out a minimum every six months by using a vacumn on the grill openings in the back and bottom of...

Страница 8: ...ts 3 Slide the leg between the Leg Ash Box and the washer align the leg with the corner of the stove and tighten the bolts Dimensions Crate Removal 24 610mm 24 610mm 28 711mm 28 711mm 29 1 8 740mm 27...

Страница 9: ...9 5 Re install the Pedestal Brace with the notched corner to the top left Install the new Ash Pan into the Pedestal Figure 2 Ped front cover removal 1 2 Leg Model 1 Remove the two screws holding the...

Страница 10: ...ut Assembly 3 Insert The Ash Cleanout System and gasket from underneath the firebox bottom up into the open hole and over the two bolts hanging down The release handle should be facing forward and on...

Страница 11: ...ECTOR AND CHIMNEY Clearances 1 This heater may be installed using a single wall connector smoke pipe or listed double wall connector 2 Clearances to combustible surfaces and materials are shown in Fig...

Страница 12: ...8mm 14 357mm 26 660mm 16 406mm 18 457mm 22 559mm 28 711mm 8 203mm 8 203mm 8 203mm Alcove Min Height 7 1 2 2 29m Max Depth 4 1 22m 5 127mm 15 381mm Single Wall Connector Residential Double Wall Connect...

Страница 13: ...gures below This protection is also required under the chimney connector and 2 51 mm beyond each side if venting horizontally into a masonry chimney Canada Only 8 203mm 18 457mm 8 203mm 8 203mm Minimu...

Страница 14: ...ers insulation and weater proofing Double Wall Connector Use a listed double wall connector Install all components to the chimney connector manufacturer s installation requirements Single Wall Connect...

Страница 15: ...istance between vent termination and roof line Also consult local National building regulations The chimney may incorporate an offset To do this safely all sections of listed connector offset elbows a...

Страница 16: ...e and building codes Have the chimney cleaned and inspected by a professional to ensure there are no cracks weak mortar or other signs of deterioration See vent manufactuer s installation instructions...

Страница 17: ...ween the outer wall of the chimney length and combustibles The inner end of the chimney length shall be flush with the inside of the masonry chimney flue and shall be sealed to the flue and to the bri...

Страница 18: ...0 61 mm in thickness with a ventilated thimble minimum 24 gauge 0 024 in 0 61 mm in thickness having two 1 in 25 4 mm air channels separated from combustibles by a minimum of 6 in 152 mm of glass fib...

Страница 19: ...rials are shown Figure 6 Clearances may be reduced with various heat insulating materials Consult local fire codes and authorities for approval NOTE Install all components to the connector and chimney...

Страница 20: ...utside combustion air for residential installation requires the unit to be secured to the structure to prevent dislodging of the air duct To draw outside air from behind the stove an outside air adapt...

Страница 21: ...s or more Wet or undried wood will cause the fire to smoulder and produce large amounts of creosote Wet wood also produces very little heat and tends to go out often DO NOT BURN Salt water wood Garbag...

Страница 22: ...1 25mm until the wood kindling is fully engulfed in flame 4 After the kindling is fully engulfed add a few small logs Close door 5 Begin normal operation after a good coal base exists and wood has ch...

Страница 23: ...has approximately 7500 BTU s per pound Experience will give you the right settings for proper combustion and efficient burning Remember the correct air inlet setting is affected by variables such as...

Страница 24: ...laced on a non combustible floor or on the ground well away from all combustible materials pend ing final disposal If the ashes are disposed of by burial in soil or otherwise locally dispersed they sh...

Страница 25: ...to operating temperature It will also shut the blower off after the fire has gone out and the unit cooled to below a useful heat output range Manual To manually operate the blower set the rocker switc...

Страница 26: ...asket Check door latch Low Heat Output 1 Wood may be wet Check wood and use drier wood if required 2 Fire too small Build a larger fire Open draft control to increase burn rate 3 Draft too low Chimney...

Страница 27: ...earest Pacific Energy dealer Contact Pacific Energy for the location of the dealer nearest you Replacement Parts Super WHEN ORDERING INCLUDE PART NUMBER WITH DESCRIPTION 16 Baffle Gasket 10pc pak 8000...

Страница 28: ...Glass Bar Set 2 pc 80000366 9 Replacement Glass c w Tape 80000373 10 Door Gasket Kit 80001640 11 Door Assembly w o glass Black 80002175 Door Assembly w o glass Brushed Nickel 80002176 Door Assembly w...

Страница 29: ...brick installation C B A D D D D D D Figure 15 Firebricks on floor 1 When installing firebricks onto the floor of a unit with an ash dump 2 small bricks A B in Fig 10 will be used on either end of the...

Страница 30: ...nds They will be held in place by two tabs per wall Install the end bricks first followed by the two center bricks The rear wall is last Tuck the rear bricks under the tabs and push back The rear bric...

Страница 31: ...SUPER CLASSIC_030818 32 31 100000813...

Страница 32: ...te http www pacificenergy net For Technical Support please contact your Dealer Printed in Canada 2018 Copyright Pacific Energy Fireplace Products LTD Reproduction adaptation or translation without pri...

Отзывы: